Chapter 6 EIP Service
6-29
Order
Set-up
Procedure
How to Set up
3
1) Name: Input the name to be used for the module.
2) IP Address: Input XBL-EIPT module’s IP.
3) Comm. Format: Set to “None” for communication based on Tag. Set "Input Data - SINT" for communication based on
Assembly Instance.
4) Connection Parameter:
Activated when "Comm Format" is selected as "None" and enter connection parameters.
Mapping has been done between this information and block index number, and the number has been allotted to Consumed
Tag input by blocks and Produced Tag output, respectively. XBL-EIPT operates as server.
(a) Assembly Instance
i) In case of Input Only
- Input Assembly Instance: ‘100+P2P index number’ in Generic EDS, ‘P2P index number’ in XBL-EIPT EDS
- Output Assembly Instance: ‘198’ (Heartbeat Assembly Instance)
ii) In case of Listen Only
- Input Assembly Instance: ‘100+P2P index number’ in Generic EDS, ‘P2P index number’ in XBL-EIPT EDS
- Output Assembly Instance: ‘199’ (Heartbeat Assembly Instance)
iii) In case of Exclusive Owner
- Input Assembly Instance: ‘100+P2P index number’ in Generic EDS, ‘P2P index number’ in XBL-EIPT EDS
- Output Assembly Instance: ‘150+P2P index number’ in Generic EDS, ‘P2P index number’ in XBL-EIPT EDS
(b) Configuration Assembly Instance: 197
(c) Size : When Generic EDS, Byte unit
When XBL-EIPT Ver1.1 EDS, Word unit
Содержание XBL-EIPT
Страница 53: ...Chapter 5 Installation of Software and communication Parameters 5 18 ...
Страница 98: ...Chapter 7 Diagnosis Function 7 11 Figure 7 3 4 FlashArea Log Screen of System Log ...
Страница 106: ...Chapter 7 Diagnosis Function 7 19 Fig 7 4 9 Remote 2 connection directly via Ethernet ...
Страница 119: ...Appendix A 12 A 3 External Dimension Dimension Unit mm XBL EIPT ...