Chapter 3 Installation and Trial-Run
3-6
3.5 Installation of Products
3.5.1 Installation of XBL-EIPT
[Figure 3.6.1] How to Install 100BASE-TX
The maximum segment distance of 100BASE-TX reaches 100m. (The distance between modules)
Straight cables and cross cables are used.
If a cross cable is used when connected between these communication modules, the time for connecting links can be
shortened.
This module doesn’t support a ring system.
When configuring a ring form, IP address switch of a module – front view must be set up at ’99.’
Then, a ring system is formed in external aspect, but the service for a ring system will not be supported.
If IP address switch is not set up at 99’after formed in a ring, data burst may happen and modules can not execute
normal actions.
Pin NO.
Signal
Straight Cable between
Cables
1:1 Cross Cable
1
TD+
1-1
1-3
2
TD -
2-2
2-6
3
RD+
3-3
3-1
6
RD-
6-6
6-2
4,5,7,8
Not used
-
-
Notice
1) 100BASE-TX cable is designed to be weak in cable structure, so only if cables are twisted (Two
wires are stranded) after No.1 (TD+) and No. 2 (TD-) wires are twisted and No. 3 and No. 6 are
twisted with each other. wiring will be strong in strength.
2) For cable terminal treatment and manufacture, consult with professional providers to install
8 Pin - RJ45 Plug
Twist Pair Cable
Содержание XBL-EIPT
Страница 53: ...Chapter 5 Installation of Software and communication Parameters 5 18 ...
Страница 98: ...Chapter 7 Diagnosis Function 7 11 Figure 7 3 4 FlashArea Log Screen of System Log ...
Страница 106: ...Chapter 7 Diagnosis Function 7 19 Fig 7 4 9 Remote 2 connection directly via Ethernet ...
Страница 119: ...Appendix A 12 A 3 External Dimension Dimension Unit mm XBL EIPT ...