Chapter 2. Functions
2-32
2.7.3
MCS – MCSCLR
The MCS n instruction starts a master control sequence. Each MCS instructions are followed by
a number (n) that shows the priority of the master control. The range of n is 0 ~ 7.
MCS 0 : High
⋅
MCS 7 : LOW
The MCSCLR n instruction ends a master control sequence. If a MCSCLR instruction is
executed, all master controls that have lower priority are cleared automatically.
MCS 0
MCS 1
MCSCLR 0 : (MCS 1 is cleared automatically)
MCSCLR 1 : Error (Improper order of MCSCLR)
When use master control, it should start from the highest priority level and end from the lowest
priority level. The MCS n and MCSCLR n instructions should be in pairs. Otherwise, a program
error occurs.