Chapter 5. Application instructions
5-108
5.16 Special module instructions
5.16.1 GET, GETP
GET, GETP
(Read data from
special module)
FUN(230) GET
FUN(231) GETP
Applicable
CPU
K200S
K300S
K1000S
Available Device
Flag
Instructions
M
P
K
L
F
T
C
S
D
#D Integer
Steps
Error
(F110)
Zero
(F111)
Carry
(F112)
O
O
O O O O*
O O
O O
GET(P)
O
9
O
* Available only when do not use computer link module or data link module
1) Functions
-
Reads the data of ‘n2’ words, which start at the address specified as [ S ] of buffer memory inside
the special module specified at ‘sl’, and stores the data into devices which begin with the device
specified at [ D ].
D
sl
n2
S
GET
sl
S
D
n2
[ S ]
n2 words
The buffer memory of
the special function
module at the slot ‘sl’
[ D ]
n2 words
CPU module
Operand setting
Slot number of special function
module is mounted
Start address of data to be read
Start address of data to be stored
Number of word to be read
sl
S
D
n2