Chapter 2. Functions
2-13
2.4
Parameter setting
2.4.1
Watch dog timer setting
(Applicable to K80S / 200S / K300S / K1000S only)
Setting range : 10msec ~ 6000msec
Setting unit : 10msec
The default value of watch dog timer is 200msec. The watch dog timer of K10S1, K10S, K30S,
and K60S is fixed as 200msec.
2.4.2
Timer area setting
(Applicable to K80S / 200S / K300S / K1000S only)
Timing unit
Setting range
Default
100ms
T000 ~ T255
T000 ~ T191
10ms
T000 ~ T255
T192 ~ T255
By setting the 100msec timer area, the 10msec timer area is automatically set as the rest of
area.
2.4.3
The latch (non-volatile) area setting
(Applicable to K80S / 200S / K300S / K1000S only)
The latch area designated by parameter setting will hold the result of operation when the CPU is
s w itched on or turned to RUN mode.
The latch area of K10S1/K10S/K30S/K60S is fixed and cannot be changed. Please refer the
Chapter 2.2 for memory configuration.
Device
Setting range
Default range
M
M0000~M191F
L
L0000~L063F
None
T(100ms)
T0000~T0191 *
T144~191 *
T(10ms)
T0192~T0255 *
T240~T255 *
C
C0000~C0255
C192~C255
K1000S
D0000~D9999
D6000~D8999
K300S
D
K200S
D0000~D4999
D3500~D4500
S
S00.00~S99.99
S80~S99
* The setting range of timer can be changed by 100msec / 10msec timer range setting.