Chapter 2. Functions
2-21
1) Parameter setting
K80S / 200S
K300S
K1000S
Priority
Type
Period
Priority
Type
Period
Priority
Type
Period
0
1
2
:
:
7
TDI0
TDI2
TDI5
:
:
INT7
10msec
25msec
100msec
0
1
2
:
:
:
13
TDI0
TDI2
TDI5
INT7
10msec
25msec
100msec
0
1
2
:
:
:
:
29
TDI0
TDI2
TDI5
INT15
10msec
25msec
100msec
a) Period is the interval of time driven interrupt occurring. It is variable from 10msec to 60000msec (60sec) by
100msec unit.
b) The priority is also used as the number of interrupt. To enable/disable the TDI5 interrupt with priority level 2,
for example, use EI/DI instruction as ‘EI 5’/ ‘DI5’.
Remark