Chapter 2. Functions
2-16
4) The example of I/O reservation
a) Actual status of module mounting
Power
supply
module
CPU
module
AC
Input
DC
Input
Relay
Output
Special
module
(Analog
input)
Empty
slot
DC
input
Relay
output
Empty
TR
output
16 Pts
32 Pts
16 Pts
16 Pts
16 Pts
16 Pts
32 Pts
b) I/O address assignment according to the I/O parameter setting
No
parameter
setting
000
~00F
010
~02F
030
~03F
040
~04F
050
~05F
060
~06F
070
~07F
080
~08F
090
~10F
AC
Input
16 Pts
DC
Input
16 Pts
Relay
Output
32 Pts
Special
AD
16 Pts
Empty
16 Pts
Empty
0 Pts
Relay
Output
16 Pts
Empty
0 Pts
TR
Output
16 Pts
Parameter
setting
000
~00F
*1)
010
~01F
*2)
020
~03F
040
~04F
050
~05F
*3)
060
~06F
070
~07F
*1) The upper 16 pts of module is disabled.
*2) The upper 16 pts (P030 ~ P03F) are used as internal relay.
*3) Since the slot is reserved as empty, the input module is disabled.
2.4.9
The output during debugging
(Applicable for K80S / 200S / K300S / K1000S)
With this parameter setting, user can decide that the result of operation will be output to external
device or not when the CPU is in DEBUG mode.
2.4.10 The slot No. for external interrupt
(Applicable for K200S only)
The K200S series has no interrupt module. Therefore, user can assign an input module as interrupt
input module and input signals applied to this module will be handled as external interrupt input.