RCI-1502 HRT Tele Boom Manual
5.1.
Verifying Operation of Sensors
Before you start calibrating the RCI-1502, you must make sure that the sensors are
working correctly and their signals are reaching the RCI-1502.
The RCI-1502 'sees' the crane and its surroundi ngs through sensors. The signals from
these sensors are represented as numbers inside the RCI-1502. The range of possible
numbers is 0 to 1023 for each sensor.
The RCI-1502 allows the user to view both the UNCALIBRATED or the CALIBRATED
signal from a given sensor
(refer to the Function Code Listing at the rear of this
manual)
.
When v iewing the UNCA LIBRATED signal from a sensor, make sure the numb er
displayed is less than 999 and is more than 32 as you work the sensor through its
working range. This is the correct operati ng range. Also make sure that the numbers
displayed in the window are chan ging in a nice, smooth manner. If you find that the
number is too unstable (i.e. chan ges by more than 10), then you should check the
connections to the RCI-1502 (refer to Section 6. “Troubleshooting”).
If the signal is less than 32, su spect a short circuit somewhere on that input channel,
e.g. the cable to the RCI-1502 has been crushed and has an internal short circuit in it.
Moisture inside the plugs can look like short circuit too.
If the count displayed in the window is 1023, look for an open circuit on that input
channel. e.g. disconnected lead.
If the sen
sors check out then you can c
ontinue on and start with the calibration
procedure. If you find any problems, check the troubleshooting guide at the end of this
manual or seek help from your nearest
LSI-Robway
distributor.
Please note that while in view mode, that is using either "VIEW UNCALIBRATED ..." or
"VIEW CALIBRATED ..." functions, the ENTER key works as a toggle switch to t urn
that channel ON or OFF. This function allows the user to temporarily turn a sensor off
if it is not needed. E.g. if you want to use the main winch only on a twin winch system;
normally, if you h ave not connected the auxil iary sensor up, the RCI-150 2 will report
an error and activate motion cut. To prevent this you can press the ENTER key, while
in "VIEW UNCALIBRATED T RANSDUCER 2 function", to turn the aux iliary channel
off.
To turn a chan nel back on, you have to re-enter the same VIEW UNCALIBRATED...
function and press the ENTER key again.
Remember that you must always end a view function by pressing the CANCEL
key.
Содержание RCI-1502 HRT
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 8: ......
Страница 14: ......
Страница 22: ......
Страница 44: ......
Страница 52: ......
Страница 56: ......
Страница 58: ......
Страница 59: ...Appendix 8 1 Data Logging on RCI Systems ...
Страница 60: ......
Страница 66: ...Data Logging on RCI Systems Example Lift Cycles ...
Страница 71: ...Appendix 8 2 Drawings ...
Страница 72: ......
Страница 73: ......
Страница 74: ......
Страница 76: ......
Страница 77: ...APPROVED BY TOL 0 0 0 1 2 3 4 55 26 2 0 7 2 8 9 1 1 1 1 0 7 5 6 2 ...
Страница 79: ...APPROVED BY TOL 0 0 0 1 22 3 4 5 6 0 22 2 1 7 8 98 1 7 8 98 7 8 98 7 8 98 1 0 9 8 3 6 8 3 ...
Страница 80: ... APPROVED BY 0 1 2 22 3 3 3 TOL 4 4 23 4 232 22 3 242 4 2 32 2 3516 7 8 7 7 9 2 3 42 4 2 ...
Страница 81: ... APPROVED BY 0 1 2 22 3 3 3 TOL 4 4 23 4 232 22 5 0 42 4 2 3617 8 9 8 8 2 ...
Страница 82: ......
Страница 83: ......
Страница 87: ......
Страница 88: ......
Страница 89: ......
Страница 90: ......
Страница 91: ......
Страница 92: ......
Страница 93: ......
Страница 94: ......
Страница 95: ......
Страница 96: ......
Страница 97: ......
Страница 98: ......
Страница 99: ......
Страница 100: ......
Страница 101: ......
Страница 103: ......
Страница 104: ......
Страница 105: ......
Страница 106: ......
Страница 107: ......
Страница 108: ......
Страница 109: ......