24
Technical catalog for Susol & Metasol ACB
Technical catalog for Susol & Metasol ACB
C
External Configuration
�
UVT installed inside of the circuit breaker opens the circuit breaker when its supply or control voltage drops below
the specified voltage. Please connect with UVT time-delay device in order to present the time-delay function
because UVT is technically instantaneous type.
�
The closing of a circuit breaker is impossible mechanically or electrically if control power not supplied to UVT.
To close the circuit breaker, 65~85% of rated voltage should be applied to both terminals of UVT coil (D1, D2).
Rated Voltage[Vn]
Power Consumption(VA or W)
Operating Voltage Range [V]
Trip Time
[ms]
24 ~ 30
48 ~ 60
100 ~ 130
200 ~ 250
-
0.65 ~ 0.85 Vn
0.4 ~ 0.6 Vn
200
5
�
Note) Operating voltage range is the min. rated standard for each rated voltage (Vh).
Less than
50ms
DC [V]
-
48
100 ~ 130
200 ~ 250
380 ~ 480
AC [V]
Inrush
Drop-Out
Pick-Up
Steady-State
Refer to the below table regarding the
length of wire when using trip coil with
24~30[V] or 48~60[V] of rated voltage
as power consumption due to inrush
current is about 200VA for coil operation.
Coil can be non-operating in case of not
corresponding with the wire specification
listed below.
The Specification of Using Wire
The Recommended Max. Wire Length
Wire Type
100%
85%
#14 AWG
(2.08mm
2
)
Operating
Voltage
48.5 m
159 ft
13.4 m
44 ft
Rated Voltage [Vn]
DC 24~30 [V]
DC/AC 48 [V]
#16 AWG
(1.31mm
2
)
30.5 m
100 ft
8.8 m
29 ft
#14 AWG
(2.08mm
2
)
233.2 m
765 ft
62.5 m
205 ft
#16 AWG
(1.31mm
2
)
143.9 m
472 ft
39.3 m
129 ft
Rated Voltage and Characteristics of UVT
External Configuration and Wiring Diagram
2. Under Voltage Trip device, UVT
Wiring Diagram
Содержание Metasol Series
Страница 32: ...31 D Digital Trip Relay D 3 Internal Circuit Diagram Internal Circuit Diagram ...
Страница 38: ...37 D Digital Trip Relay D Ground Fault Protection 4 Relay Function ...
Страница 39: ...38 Technical catalog for Susol Metasol ACB Technical catalog for Susol Metasol ACB D D IDMTL ...
Страница 40: ...39 D Digital Trip Relay D PT A Curve 4 Relay Function ...
Страница 136: ...K 136 138 1 Control Circuit 2 External Dimension Control Circuit and Dimension 135 ...
Страница 153: ...152 Technical catalog for Susol Metasol ACB Technical catalog for Susol Metasol ACB Memo ...
Страница 154: ...153 Technical Materials Memo ...