74
Technical catalog for Susol & Metasol ACB
Technical catalog for Susol & Metasol ACB
F
Table A. The Compensation of Rated Current According to Ambient Demperature
40
℃
200A
400A
630A
800A
1,000A
1,250A
1,600A
2,000A
630A
800A
1,000A
1,250A
1,600A
2,000A
2,500A
3,200A
4,000A
4,000A
5,000A
4,000A
5,000A
6,300A
5t
�
40
�
2ea
5t
�
50
�
2ea
5t
�
60
�
2ea
5t
�
80
�
2ea
5t
�
100
�
2ea
5t
�
100
�
3ea
5t
�
40
�
2ea
5t
�
50
�
2ea
5t
�
60
�
2ea
5t
�
80
�
2ea
5t
�
100
�
2ea
5t
�
100
�
3ea
5t
�
100
�
4ea
10t
�
100
�
3ea
10t
�
100
�
4ea
10t
�
100
�
4ea
10t
�
125
�
4ea
10t
�
100
�
4ea
10t
�
125
�
4ea
10t
�
150
�
4ea
200A
400A
630A
800A
1,000A
1,250A
1,600A
2,000A
630A
800A
1,000A
1,250A
1,600A
2,000A
2,500A
3,200A
4,000A
4,000A
5,000A
4,000A
5,000A
6,300A
45
℃
200A
400A
630A
800A
1,000A
1,250A
1,600A
2,000A
630A
800A
1,000A
1,250A
1,600A
2,000A
2,500A
3,200A
3,900A
3,900A
5,000A
4,000A
5,000A
6,300A
50
℃
200A
400A
630A
800A
1,000A
1,250A
1,600A
1,950A
630A
800A
1,000A
1,250A
1,600A
2,000A
2,500A
3,100A
3,800A
3,800A
4,900A
4,000A
5,000A
6,200A
55
℃
200A
400A
630A
800A
1,000A
1,250A
1,550A
1,900A
630A
800A
1,000A
1,250A
1,600A
2,000A
2,400A
3,000A
3,700A
3,700A
4,800A
3,900A
4,900A
6,100A
60
℃
200A
400A
630A
800A
1,000A
1,250A
1,500A
1,850A
630A
800A
1,000A
1,250A
1,600A
2,000A
2,300A
2,900A
3,600A
3,600A
4,700A
3,800A
4,800A
6,000A
40
℃
200A
400A
630A
800A
1,000A
1,250A
1,600A
2,000A
630A
800A
1,000A
1,250A
1,600A
2,000A
2,500A
3,200A
4,000A
4,000A
5,000A
4,000A
5,000A
6,300A
45
℃
200A
400A
630A
800A
1,000A
1,250A
1,600A
2,000A
630A
800A
1,000A
1,250A
1,600A
2,000A
2,500A
3,200A
3,950A
3,950A
5,000A
4,000A
5,000A
6,300A
50
℃
200A
400A
630A
800A
1,000A
1,250A
1,600A
2,000A
630A
800A
1,000A
1,250A
1,600A
2,000A
2,500A
3,150A
3,850A
3,850A
4,950A
4,000A
5,000A
6,250A
55
℃
200A
400A
630A
800A
1,000A
1,250A
1,600A
1,950A
630A
800A
1,000A
1,250A
1,600A
2,000A
2,450A
3,050A
3,750A
3,750A
4,850A
3,950A
4,950A
6,150A
60
℃
200A
400A
630A
800A
1,000A
1,250A
1,550A
1,900A
630A
800A
1,000A
1,250A
1,600A
2,000A
2,350A
2,950A
3,650A
3,650A
4,750A
3,850A
4,850A
6,050A
2,000AF
(AN, AS,
AH-D)
5,000AF
(AS-F)
6,000AF
(AN, AS,
AH-G)
4,000AF
(AN, AS,
AH-E)
FRAME
Rated
Current
ACB
Terminal
Applicable
Busbar Size
5t
�
30
�
2ea
Horizontal Type
Vertical Type
15t
�
50
�
1ea
15t
�
75
�
1ea
10t
�
100
�
3ea
20t
�
125
�
2ea
20t
�
125
�
2ea
20t
�
150
�
2ea
20t
�
75
�
1ea
4. Service Condition
If under ordinary conditions the following normal working conditions are all satisfied, Susol ACB should be used under this condition
unless otherwise specified.
1) Ambient temperature : A range of max. +40° to min. -5° is recommended. However, the average temperature of 24 hours
does not 35°.
2) Altitude : 2,000m or less.
3) Environmental conditions : The air must be clean, and the relative humidity does not exceed 85% at a max. of +40° and
90% at 20°. Do not use and store in presence of corrosive or ammonia gas.
(H2S °¬ 0.01ppm, SO2 °¬ 0.01ppm, NH3 °¬ a few ppm)
4) Installation conditions : When installing Susol ACB, refer to catalogue or the installation instructions in the instruction manual.
5) Storage temperature : A range of max. +60° to min. -20° is recommended. However, the average temperature of 24 hours
does not 35°.
6) Replacement : Approx. 10 years (depends on number of breaking of over current or service condition). Please see maintenance
and inspection for further detail.
Normal Service Conditions
In the case of special service condition, modified air circuit breakers are available. Please specify when ordering. Service life may be
shorter, it depends on service conditions.
1) Special environmental conditions : If it is used at high temperature and/or high humidity, the insulation durability and other
electrical or mechanical features may deteriorate. Therefore, the breaker should be specially treated. Moisture fungus treatment
with increased corrosion-resistance is recommended. When using products under this condition, please contact LS service
team or nearest sales representatives.
2) Special ambient temperature : If the ambient temperature e 40°, reduce the continuous conducting current for a
use referring to Table. A.
3) Special altitude : If it is used at the 2,000m or higher the heat radiation rate is reduced and the operating voltage, continuous
current capacity and breaking capacity are decreased. Moreover the durability of the insulation is also decreased owing to
the atmospheric pressure. Contact us for further detail.
Special service conditions
Содержание Metasol Series
Страница 32: ...31 D Digital Trip Relay D 3 Internal Circuit Diagram Internal Circuit Diagram ...
Страница 38: ...37 D Digital Trip Relay D Ground Fault Protection 4 Relay Function ...
Страница 39: ...38 Technical catalog for Susol Metasol ACB Technical catalog for Susol Metasol ACB D D IDMTL ...
Страница 40: ...39 D Digital Trip Relay D PT A Curve 4 Relay Function ...
Страница 136: ...K 136 138 1 Control Circuit 2 External Dimension Control Circuit and Dimension 135 ...
Страница 153: ...152 Technical catalog for Susol Metasol ACB Technical catalog for Susol Metasol ACB Memo ...
Страница 154: ...153 Technical Materials Memo ...