1. Externals
�
Charge the closing spring of a circuit breaker by the
external power source. Operating voltage range is in
the range of 85%~110% Vn (IEC 60947).
�
�
Common use for all types
Charging Motor
Motor
2. The Classification of Motor
3. Installation Method
1) Connect the manual handle axis of mechanism in
main body with the main axis of charging motor.
Main Axis
Gear
Fully Charged
Contact
Main Body
Charging Motor
Mechanism
Input voltage (Vn)
Load current (max.)
Starting current (max.)
Load (rpm)
Charging Time (sec.)
Dielectric strength
Using temperature range
Using humidity range
Endurance
Fully Charged Contact
5 times of load current
15000 ~ 19000 rpm
Time
5 sec
2kV/min
-20
。
~ 60
。
Max. RH 80% (No dew condensation)
15,000 cycle (Load connection, 2 times /min, Operating time : 5 sec per a operation)
10A at 250VAC
Motor
DC24/30V DC48/60V
AC380V AC440/480V
AC/DC100/130V AC/DC200/250V
5A
3A
0.3A
0.3A
1A
0.5A
Содержание Metasol Series
Страница 32: ...31 D Digital Trip Relay D 3 Internal Circuit Diagram Internal Circuit Diagram ...
Страница 38: ...37 D Digital Trip Relay D Ground Fault Protection 4 Relay Function ...
Страница 39: ...38 Technical catalog for Susol Metasol ACB Technical catalog for Susol Metasol ACB D D IDMTL ...
Страница 40: ...39 D Digital Trip Relay D PT A Curve 4 Relay Function ...
Страница 136: ...K 136 138 1 Control Circuit 2 External Dimension Control Circuit and Dimension 135 ...
Страница 153: ...152 Technical catalog for Susol Metasol ACB Technical catalog for Susol Metasol ACB Memo ...
Страница 154: ...153 Technical Materials Memo ...