49
D
: Power Production
: Power Consumption
3. Apparent Power Calculation
1) Apparent power defines as current RMS value x voltage RMS value.
2) In case of no harmonic factors, the power equation formulates.
3) However, if harmonic is included, the equation of power does not formulate.
4) Thus, to avoid confusion of P and S type users, evaluate active and reactive power first and then evaluate
apparent power by using, not by using current RMS value x voltage RMS value.
4. Power Factor Calculation
1) Evaluate the size of power factor with the Pf = active power/apparent power equation.
5. Indication of Power and Power Factor According to Phase
6. Electric Energy - Bidirectional Metering
Integrate separately by classifying power into receiving and transmission.
1. Active electric energy, reactive electric energy, reverse active electric energy, reverse reactive electric energy
2. Refer to above figure for classification of corresponding factors.
3. Concerning the size of power factor, the symbols have the meaning as the above figure.
I
V
I
V
I
V
I
V
1 quadrant
Power > 0
Reactive Power < 0
PF > 0
90
0
180
270
4 quadran
Power > 0
Reactive Power > 0
PF > 0
3 quadrant
Power < 0
Reactive Power > 0
PF < 0
2 quadrant
Power < 0
Reactive Power < 0
PF < 0
S
=
√
P
+
Q
2
2
S
=
√
P
+
Q
2
2
Digital Trip Relay
5. Measurement Function
Lag
Lead
Lag
Lead
Содержание Metasol Series
Страница 32: ...31 D Digital Trip Relay D 3 Internal Circuit Diagram Internal Circuit Diagram ...
Страница 38: ...37 D Digital Trip Relay D Ground Fault Protection 4 Relay Function ...
Страница 39: ...38 Technical catalog for Susol Metasol ACB Technical catalog for Susol Metasol ACB D D IDMTL ...
Страница 40: ...39 D Digital Trip Relay D PT A Curve 4 Relay Function ...
Страница 136: ...K 136 138 1 Control Circuit 2 External Dimension Control Circuit and Dimension 135 ...
Страница 153: ...152 Technical catalog for Susol Metasol ACB Technical catalog for Susol Metasol ACB Memo ...
Страница 154: ...153 Technical Materials Memo ...