47
D
Voltage / Current Unbalance for P, S Type
U
=
3
avg
U
+ +
R
U
S
U
T
1. Definition of Unbalance Factor 1
2. Definition of Unbalance Factor 2
1) Umax is the largest value among 3 phase system (R, S, T)
2) Uavg is average of 3 phase system( (R + S + T) / 3 )
3) Unbalance percentage is defined as (Umax - Uavg) / Uavg.
4) It can be used for simple and practical purposes, but can not imply meanings behind phase.
T phase
Positive Phase
Negative Phase
Zero Phase
T phase
=
+
+
T phase
T phase
R phase
Uavg
R
S
T
Umax
R phase
R phase
R phase
S phase
S phase
S phase
S phase
Digital Trip Relay
5. Measurement Function
1) Positive-phase-sequence component means a fundamental phase rotation of power system.
2) Negative-phase-sequence component means a phase rotation inversely to power system.
3) Zero-phase-sequence component means in-phase on R/S/T phases regardless of phase rotation of power system.
4) 3 phase system in power system can be displayed as positive-phase + negative-phase + zero-phase-
sequence component.
5) After interpreting 3 phase as positive-phase, negative-phase, and zero-phase sequence component, and
define negative/positive phase as unbalance.
6) Even though the concept is based on definition, there is unstable part in figure due to complexity of mathematic.
Apply on P
,S T
ype
Содержание Metasol Series
Страница 32: ...31 D Digital Trip Relay D 3 Internal Circuit Diagram Internal Circuit Diagram ...
Страница 38: ...37 D Digital Trip Relay D Ground Fault Protection 4 Relay Function ...
Страница 39: ...38 Technical catalog for Susol Metasol ACB Technical catalog for Susol Metasol ACB D D IDMTL ...
Страница 40: ...39 D Digital Trip Relay D PT A Curve 4 Relay Function ...
Страница 136: ...K 136 138 1 Control Circuit 2 External Dimension Control Circuit and Dimension 135 ...
Страница 153: ...152 Technical catalog for Susol Metasol ACB Technical catalog for Susol Metasol ACB Memo ...
Страница 154: ...153 Technical Materials Memo ...