L-INX User Manual
239
LOYTEC
Version 4.0
LOYTEC electronics GmbH
2.
In the
Device Config
tab enable the Modbus check boxes on the desired ports as shown
in Figure 186. Setting the check box enables Modbus on that port. Edit the Modbus
communication settings.
3.
If slave mode is enabled, you may change the default Modbus register layout in the
Modbus Slave Register Configuration
box.
4.
Click the
Download
button to activate the changes in the configuration.
Figure 186: Project settings for Modbus.
Important:
If the Modbus port is deactivated via the checkbox or a firmware or model version is
chosen, which does not support Modbus, the entire Modbus configuration is deleted. In
this case a dialog is displayed, which has to be confirmed.
11.4.2 Data Point Manager for Modbus
The Configurator uses a central concept to manage data points. The data point manager is
used to select, create, edit and delete data points. The dialog is divided into three sections:
The folder list (Figure 187),
The data point list (Figure 188),
And a property view.