L-INX User Manual
149
LOYTEC
Version 4.0
LOYTEC electronics GmbH
contents of user-defined types, the
device resource files
supplied by the vendor must be
added to the resource catalog on your PC.
Once the resource files are installed, the CEA-709 network scan and the LNS scan will
display the user-defined types from the resource files. Those data points can be used on the
device like regular, standard-type data points. Also manual creation of UNVTs can be
performed.
To Manually Create a Static UNVT
1.
Perform the steps to manually create a static NV as described in Section 6.7.7.
2.
When the
Create New NV
dialog appears, change the resource file from
‗STANDARD‘ in the
Resource File
drop-down box to the desired, user-defined
resource file
3.
Then select the desired UNVT from the
Type
drop-down list below. This list will
display the types of the selected resource file only.
4.
Click
Create Static NV
to create the UNVT on the device.
6.9 BACnet Configuration
6.9.1 Scan for BACnet Objects
LOYTEC devices also support an online network scan on the BACnet network. In this scan
the device searches for other devices on the BACnet network and pulls in the BACnet
object information of these devices. These BACnet objects can then be used on the device
as the basis for client mapping.
To Scan for BACnet Objects
1.
Go to the
Datapoints
tab.
2.
Select the folder
BACnet Network Scan
3.
Right-click on that folder and select
Scan BACnet Network…
. This opens the
BACnet Network Scan dialog as shown in Figure 131.