M25 – USER ALARMS (UAn, n=1…8) UoM Default Range
P25.n.01 Alarm source OFF OFF-INPx-OUTx-
LIMx-REMx
P25.n.02 Channel number source x 1 OFF / 1-99
P25.n.03 Text UAn (text – 20 char)
Note: This menu is divided into 8 sections for user alarms UA1...UA8.
P25.n.01
– Defines the digital input or internal variable that generates the user alarm when it is activated.
P25.n.02
– Channel number x relative to the previous parameter.
P25.n.03
– Free text that appears in the alarm window.
Application example: User alarm UA3 must be generated when input INP5 closes and must display the message ‘Doors open’.
In this case, set the section of menu 3 (for alarm UA3) as follows:
P25.3.01 = INPx
P25.3.02 = 5
P25.3.03 = Doors open.
M26 – ALARM PROPERTIES (ALAn, n=1…23) Default Range
P26.n.01 Alarm enable (see ALARMS PROPERTY TABLE) OFF – ON
P26.n.02 Retentive (see ALARMS PROPERTY TABLE) OFF - RET
P26.n.03 Operating mode (see ALARMS PROPERTY TABLE) AUT-MAN / AUT
P26.n.04 Global alarm 1 (see ALARMS PROPERTY TABLE) OFF – GLB1
P26.n.05 Global alarm 2 (see ALARMS PROPERTY TABLE) OFF – GLB2
P26.n.06 Global alarm 3 (see ALARMS PROPERTY TABLE) OFF – GLB3
P26.n.07 Step disconnection (see ALARMS PROPERTY TABLE) OFF
IMMEDIATE
SLOW
P26.n.09 Inhibition from input (see ALARMS PROPERTY TABLE) OFF - INH
P26.n.10 Modem call (see ALARMS PROPERTY TABLE) OFF - MDM
P26.n.11 Not shown on LCD (see ALARMS PROPERTY TABLE) OFF - NOLCD
P26.n.12 Alarm delay (see ALARMS PROPERTY TABLE) OFF/ 1-120
P26.n.13 Delay UoM (see ALARMS PROPERTY TABLE) MIN-SEC
P26.n.01
–
Enabled -
General enabling of the alarm. If the alarm is not enabled, it is not considered as if it did not exist.
P26.n.02
–
Retentive
- Remains stored even if the cause of the alarm has been eliminated.
P26.n.03
–
Operating mode
– Operating mode in which the alarm is generated.
P26.n.04...P26.n.06
–
Global alarm 1 -2 -3
– Activates the output assigned to this function.
P26.n.07
–
Step disconnection mode
– Defines whether and how the capacitor steps must be disconnected when the alarm is present. Choice among:
OFF
= no disconnection;
SLOW
= gradual disconnection;
FAST
= Immediate disconnection.
P26.n.09
–
Inhibition
- The alarm can be temporarily disabled by activating an input that can be programmed with the inhibit alarm function.
P26.n.10
–
Modem call
- A modem is connected as configured in setup.
P26.n.11
–
No LCD
- The alarm is normally managed, but not viewed on the display.
P26.n.12 – P26.n.13
–
Delay time
- Time delay in minutes or seconds before the alarm is generated.
G