LONGHORN LHD6000 Скачать руководство пользователя страница 15

The master controller: Wire zone: 01~16(9~16 zones is extended wire zones)

Wireless zone: 21~28

Help: 17

Duress code: 18

Tamper: 30

The keypad:  Keypad 1: two-way zone: 31, 41, 42

Keypad 2: two-way zone: 32, 43, 44

Keypad 3: two-way zone: 33, 45, 46

Keypad 4: two-way zone: 34, 47, 48

When the keypad stops working without being cancelled, the master controller will alarm. Use anti-tamper zones: 
51, 52, 53, 54 respectively indicating correspondent keypad disconnected.

8.2 Definitions of zone number

9. Keypad operation

Operation display explanation

1. LED displays real-time clock, for example 11:25.

2. In alarm status, the left of the LED displays two digits "- -" and the right displays alarm zone numbers. Buzzer 

chirps continually, at the same time correspondent indicator is on. For example, if NO.17 zone alarms, the LED 
displays "- - 1 7".

3.  Press  the  "Program"  key  when  system  is  in  disarmed  status  and  password  input  is  right.  LED  displays'-  -  -  -' 

indicate the programming status. The commands and perimeters input will be displayed from the left to the right. 
When input more than three digits, the digits will move to the left, the last digit will display "-" but not itself .For 
example, when input '1 2 3', displays '1 2 3 -', while input a '4' more, displays '2 3 4 -'.

4.  In  the  programming  status,  press  '#'  key  to  disposal  the  command  and  parameters  .  If  the  command  and 

parameters input is fault or can not be performed, the system will exit the programming status automatically and 
displays  clock,  at  the  same  time,  buzzer  beeps  5  times;  Input  the  right  command,  buzzer  beeps  twice  and 
displays '- - - -'. It is able to exit the programming status by pressing '#' key return to the clock status.

5.  Programming  or  inputting  passwords,  press  '*'key  to  delete  a  digit. After  deleted  all  digits,  press  '*'  key  to  exit 

present status and return to display clock.

6. When programming, if the user does not press key in one minute, the system will exit the programming status 

and return to display clock.

9.1 Password input

Operation:

 "Disarm" or "Program" key

user password

'#' confirmation.

After  pressing  "  DISARM  "  or  "  PROG  "  key,  the  system  enters  password  input  status  '-  -  -  -'.  Continue  to  input 
password, and LED displays 'H' from the left to the right, the right side displays '-'. For example, when input 2 digits, 
LED displays 'H H - - '. If password is in error, the system exits input status and displays clock and buzzer beeps 5 
times. If input wrong password for 5 times continuously, the keypad can not operate with password in 30 minutes. 
Restart the system unlock the keypad .when the keypad is locked, press any keys in the keypad the backlight will 
flashes twice. User password is 0808 in factory setting.

9.2 Function key operation

9.2.1 Arm-away

Press  'AWAY   key,  then  the  keypad  buzzer  beeps  continuously  and  the  status  indicator  is  on.  The 

system  enters  arm-away  delay.  When  arm  delay  is  over,  buzzer  stops  beeping  and  the  system  enters 

9

12

9.3.1 Alarm telephone number Setting/canceling                                                   Input: 11 XY...Y

(1) Set alarm phone number

Operations: (PROG

user password

#)

11

XY...Y

#

Bracket means in programming status, it is not necessary to input 'PROG 

 user password

#', enter command 

status directly.

Parameters  setting:

  X=1~6,  indicates  1~6  groups  telephone,  1  is  alarm  number  of  the  alarm  center,  2~6  are 

personal phone numbers.

Y...Y:

 indicates phone number needed to dial (1~15 digits), phone number is null in factory setting.

Functions: 

The system can be set 6 groups of alarm phone number. NO. 1 is for the alarm center. If user sets the 

first  number,  when  alarm  happens,  the  system  will  announce  the  alarm  center  and  sent  out  alarm  information 
according  to ADEMCO Agreement.  If  user  does  not  open  service  of  the  alarm  center,  the  system  begins  to  dial 
number  from  NO.2  according  to  alarm  information  set.  After  putting  through  a  phone,  the  system  plays 
corresponding  alarm  sound.  If  user  does  not  deal  with  alarm  information,  the  system  will  continually  dial  the 
number set 5 times.(refer to Remote phone operation).

For  example:

if  user  wants  to  set  NO2&3,  operation  as  followed:  Program

User  password

#

11

2

phone 

number

#

11

3

phone number

#

Note:

 In duress alarm status, the telephone will not dial the second, the third and the fourth these three groups of 

telephones but the alarm center, the fifth, the sixth group of telephones. Recommended: the fifth, the sixth group of 
telephone numbers should not be set like the personal mobile phone number.

(2) Alarm telephone number cancel

Operations:

 

(PROG

User  password

#)

11

X

#

,  Parameters  setting:  X=1~6,  indicates  1~6  groups 

telephone 1 for the alarm center, 2~6 for personal telephone numbers.

9.3.2 User address code setting                                                                                  Enter:20 XXXX

Operations: (PROG

user password

#)

20

XXXX

#

Parameter definition: 

XXXX = 4 digits user code. The factory setting is 1234.

Functions: 

After setting user code, when alarm happens, the alarm center will distinguish which master controller is 

9.3.3 User password modification                                                                               Enter:21 XXXX

Operations: (PROG

user password

#)

21

XXXX

#

Parameters definition:

XXXX = 4 digits code. The factory setting is 0808

Functions: 

User  can  modify  user  password  which  ensure  user's  absolute  authority  to  operate  the  system.  User 

must hold password to operate the system. After setting password, user should ensure its safety and reliability.

Duress password:

 When user is under duress, user can press 'Disarm' key and input duress password. The control 

panel will display 'Disarm', send out alarm message to the alarm center or the receiver and keep alarm record (the 
zone number is 18). Duress password can be used to disarm but set parameters. Duress password is the last digit 
of user password plus 1, no carry, i.e. 9+1=0.

For  example: 

If  user  password  is  8889,  corresponding  duress  password  is  8880;  if  user  password  is  9999, 

corresponding duress password is 9990.

Restore  password  in  factory setting:

 Hardware  restores factory setting. There  is a  jumper 'CB400' on  PCB of the 

master  controller.  Normally  the  jumper  is  in  'USE'  mode,  if  user  forgets  password,  he/she  should  turn  off  system 
power, turn jumper to 'DEFAULT' mode, then enable the system again to restore user password in factory setting. 
After  the  system  is  initialized  successfully,  user  should  turn  jumper  to  'USE'  mode,  or  the  system  will  restore 

Содержание LHD6000

Страница 1: ...er Shenzhen Longhorn Technology Co Ltd Add Longhorn Hi Tech Estate TongFuyu Industrial Avenue Longhua Shenzhen G D China Post number 518109 Tel 800 830 8196 Fax 86 755 28140429 E mail service long horn com Web address http www long horn com ...

Страница 2: ...INSTALLATION MANUAL ...

Страница 3: ...acked in a box as followed Open the box and check it carefully If finding deficiency please fetch the provider in time Note There are two anti tamper switches of control panel twenty four EOL resistances 2 2k two keys for cabinet of control panel telephone line telescopic antenna keypad anti tamper switch spring screw expansion pipe and keypad fixed iron stand connecting line installation frame ke...

Страница 4: ...5mAh Potential reasons Solutions Types of fault Code learn unsuccessful Different detectors use the same code learn The different carrier frequency of the detector and the control panel The detector does not work normally Cancel this zone check the code learn again make sure the detector code learn has not been used Change the detector and try again Confirm carrier frequency of the detector Cancel...

Страница 5: ...Weekly testing is required to ensure proper operation of the system 14 Troubleshooting The controller plug is not inserted in DC socket or it is not connected well Check the connection of the plug or replace the socket Check whether keypad is wired incorrectly or not and wire Keypad is wired incorrectly Telephone can not work normally as the system is connected into telephone network Few ringing a...

Страница 6: ...ATION OF USER ARM DISARM Number Operation of using keypad without password such as arm away disarm and arm stay User password to arm disarm by using keypad or remote telephone Operation code of Arm disarm by using keypad or remote telephone Remote controller arm disarm Alarm for disarm arm operation by using telephone numbers from 2 to 6 Using duress code to disarm press 98 to send a disarm inform...

Страница 7: ...to alarm user can press 3 to disarm and then press 1 to arm after hearing alarm voice 11 3 Telephone arm stay After hanging up the system press user password 2 to arm When emergencies happen user has to disarm first and then arm the system again For example if user password is 1234 press 12342 When the master controller dials to alarm user can press 3 2 to arm after hearing sound 11 4 Telephone fi...

Страница 8: ...ll in armed state 24 hour zone No matter armed or disarmed it is in effective detecting status It is usually used in fire alarm plunder alarm and other emergent alarm which can be cancelled only by password holder 19 10 Wireless remote controller operation Wireless remote controller have 4 keys which can achieve operations of arm away stay disarm and panic alarm without user password Press keys on...

Страница 9: ...ng Functions Connect a horn to the control panel play 8 alarm type records and user address record The recorder 9 3 28 Event record reading Enter 80 XX Operations PROG user password 80 XX Parameters definition XX 01 40 event records Functions The system stores 40 event records which can be inquired by user any time The system records alarm in zones but no fault alarm for AC power loss low battery ...

Страница 10: ... GND Z2 GND Wiring board figure 5 5 Keypad installation The keypad provides two modes of installation for various surroundings concealed installation fixed on the wall by 86 box wiring board and bracket and open installation fixed on the wall by screws Bracket installation figure 120 80 10 6 33 20 30 Bracket figure Unit mm Wall Bracket Gang socket Tamper switch Fixed card hole fixed iron stand Fix...

Страница 11: ...sketch Locating hole Terminal slot Anti tamper switch spring hole Card slot Buzzer hole Dial switch hole Interface slot Card slot Outlet slot 5 5 2 Surface installation Connect keypad to the control panel and fix the keypad on the wall through the four locating holes at the rear cover of keypad Keypad PCB wiring sketch CPU V_KEYGND Z2 GND Z1 B A V_AUX Buzzer Wiring slot Wiring terminal Dial switch...

Страница 12: ...re keypads to avoid address clash It can be reached by adjusting address dial up switch on keypad back See the table below Note Dial up switch ON terminal is ON another terminal is OFF 1 OFF OFF ON ON 2 ID OFF ON OFF ON 1 NO1 keypad 2 NO2 keypad 3 NO3 keypad 4 NO4 keypad 15 9 3 15 Date setting Enter 33 XXXX Operations PROG user password 33 XXXX Parameters definition XXXX is for date setting XXXX m...

Страница 13: ...s XX 00 no delay XX 01 10 seconds 5 11 Telescopic antenna installation When telephone line is lost in self checking status the control panel will alarm for telephone line lost Loss indicator will be on and buzzer chirps twice in every two minutes until chirps 15 times 30minutes When telephone line is restored Loss indicator will be off 4 Status indicator Keep on when the system is in arm away stat...

Страница 14: ...ts the system begins to accept user remote operation 9 3 6 Bell on off setting Enter 24 X Operations PROG user password 24 X Parameters definition X 1 on X 0 off The factory setting is X 1 on Functions User can choose using bell alarm or not Setting the bell it will be on when the system alarms otherwise only buzzer on keypad chirps 9 3 7 Timed auto arm auto disarm option Enter 25 X Operations PRO...

Страница 15: ...G user password 11 XY Y Bracket means in programming status it is not necessary to input PROG user password enter command status directly Parameters setting X 1 6 indicates 1 6 groups telephone 1 is alarm number of the alarm center 2 6 are personal phone numbers Y Y indicates phone number needed to dial 1 15 digits phone number is null in factory setting Functions The system can be set 6 groups of...

Страница 16: ...faultsvaluesrestoration Keypadlogout 36 X Y 40 X Y 61 X 62 X 63 X 64 X 65 X 66 X 70 0 71 X 80 X 910 920 930 940 950 960 990 X 1 3 NO Xauto disarmmoment Y hourminute 4digits X 01 16 16wirezonesand 09 16areextendedwire zones X 21 28 8wireless zones X 41 48 4keypads have8wirezones TypecodeY 1 8 X 21 28 NO Xdetectorin wirelesszone X 21 28 NO Xdetectorin wirelesszone X 1 5 NO Xwirelessremote controller...

Отзывы: