background image

7

Continued  manual  resetting  of  high  limit  control,  preceded  by 

higher  than  usual  water  temperature  is  evidence  of  high  limit 

switch operation. The following is a possible reason for high limit 

switch operation:

•  A malfunction in the thermostatic controls would allow the gas 

valve to remain open causing water temperature to exceed the 

thermostat setting. The water temperature would continue to 

rise until high limit switch operation.

Contact your dealer or service agent if continued high limit switch 

operation occurs.

DIGITAL THERMOSTAT

FIGURE 3

ELECTRONIC IGNITION CONTROL

Each heater is equipped with a Honeywell ignition module. The 

solid state ignition control, fig.4, ignites the pilot burner gas by 

creating a spark at the pilot assembly.  Pilot gas is ignited and 

burns during each running cycle.  The main burner and pilot gases 

are cut off during the OFF cycle.  Pilot gas ignition is proven by the 

pilot sensor.  Main burner ignition will not occur if the pilot sensor 

does not first sense pilot ignition.

HONEYWELL IGNITION MODULE

S8600M Continuous Re-Try

FIGURE 4

AUTOMATIC FLUE DAMPER DEVICE

All  units  are  equipped  with  an  automatic  flue  damper  that 

reduces heat loss during the OFF cycles. The automatic flue 

damper  drive  assembly  is  a  field  replaceable  part  and  may 

be  obtained  by  contacting  your  Lochinvar  dealer,  distributor 

 

or,  Parts  Department,  300  Maddox  Simpson  Pkwy,  Lebanon, 

TN  37090,  Phone:  615-889-8900  •  Fax:  615-882-2918,  email: 

[email protected], www.Lochinvar.com.
Each automatic flue damper drive assembly is equipped with a 

“Service Switch”, as shown in figure 5.

FIGURE 5

The  “Service  Switch”  has  2  positions:  AUTOMATIC 

OPERATION  and  HOLD  OPEN  DAMPER.    For  normal 

operation  the  switch  should  be  in  the  AUTOMATIC 

OPERATION position.

If there is a problem with the damper the “Service Switch” can 

be placed in the HOLD OPEN DAMPER position.  When the 

switch is placed in the HOLD OPEN DAMPER position the 

damper disc will rotate to the open position and the heater 

may be used until vent assembly is repaired or replaced.  DO 

NOT turn the damper disc manually; damage will occur to 

the drive assembly if operated manually.  Refer to TESTING 

DAMPER OPERATION section of this manual for additional 

information. 

CIRCULATING PUMP

A circulating pump is used when a system requires a circulating 

loop or there is a storage tank used in conjunction with the heater.  

Refer to the piping diagrams in this manual for electrical hookup 

information and install in accordance with the current edition of 

the 

National Electrical Code NFPA 70. For Canada refer to the 

Canadian Electrical Code CSA C22.1.

Only all bronze circulating pumps should be used with commercial 

water heaters.

Although  circulating  pumps  are  oiled  and  operated  by  the 

manufacturer  some  circulators  must  be  oiled  again  before 

operating.  Please refer to manufacturer’s instructions.  

DISHWASHING MACHINE REQUIREMENT

These  appliances  meet  the  NSF  Standard  5  for  sanitary 

installations  when  used  with  the  following  leg  kits,  Part 

#9003425205.

All  dishwashing  machines  meeting  the  National  Sanitation 

Foundation requirements are designed to operate with water flow 

pressures between 15 and 25 psi (103 kPa and 173 kPa).  Flow 

pressures above 25 psi (173 kPa), or below 15 psi (103 kPa), will 

result in improperly sanitized dishes. Where pressures are high, 

a water pressure reducing or flow regulating control valve should 

be used in 180°F (82°C) line to the dishwashing machine, and 

should be adjusted to deliver water between these limits.

Содержание CG 120 THRU 400A

Страница 1: ...E CAUTION TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION RELATIVE TO YOUR SAFETY PLEASE READ THOROUGHLY BEFORE INSTALLING AND USING THIS APPLIANCE Thank you for buying this energy efficient wate...

Страница 2: ...58 kW Hr 379 L 183 cm 12 cm 165 cm 142 cm 50 cm 58 cm 1 2 143 cm 15 cm 77 cm 1 50 2 00 2 00 1 50 2 00 2 00 286 Kg 329 Kg CG N L 250 000 BTR Hr 100 Gal 72 00 4 50 65 13 55 87 19 75 23 1 2 56 38 8 30 2...

Страница 3: ...1745 1393 1162 996 871 776 697 632 583 538 500 CG N L 199 000 BTUH 100 Gal 80 643 482 386 322 276 241 214 193 175 161 148 132 199100 A 58 Kw Hr 379 L 2434 1825 1461 1219 1045 912 810 731 662 609 560...

Страница 4: ...bleshooting Guide 32 Operational Checklist 33 Limited Warranty 34 Page Page FOREWORD These designs comply withANSI Z21 10 3 CSA4 3 as an automatic circulating or automatic storage tank type water heat...

Страница 5: ...ve and heavier than air It collects first in the low areas making its odor difficult to detect at nose level If LP gas is present or even suspected do not attempt to find the cause yourself Go to a ne...

Страница 6: ...nt with orifices sized for the particular installation elevation Correct orifice sizing and parts may be obtained from Lochinvar LLC When ordering be sure to state the model number and the altitude of...

Страница 7: ...TION and HOLD OPEN DAMPER For normal operation the switch should be in the AUTOMATIC OPERATION position If there is a problem with the damper the Service Switch can be placed in the HOLD OPEN DAMPER p...

Страница 8: ...n on combustible flooring in an alcove when the minimum clearance from any combustion construction are followed as indicated in figure 6 and Table 2 The National Sanitation Foundation also recommends...

Страница 9: ...ee MAINTENANCE section for details of tank cleanout procedure AIR REQUIREMENTS REFER TO THE CURRENT EDITION OF THE NATIONAL FUEL GAS CODE ANSI Z223 1 NFPA 54 FOR CANADA CONSULT NATURAL GAS AND PROPANE...

Страница 10: ...AND ASPHYXIATION Heater must be protected from freezing downdrafts Remove all soot or other obstructions from the chimney that will retard a free draft Type B venting is recommended with these heater...

Страница 11: ...CG N L 180080 200080 200100 199100 Input 180 000 190 000 199 000 Btuh Total Vent Height Feet Draft Hood 6 6 8 10 15 20 30 50 100 Input Btuh Rise Vent Connector Diameter in inches 180 000 1 Ft 8 8 8 8...

Страница 12: ...N L 305065 A Input 305 000 Btuh Total Vent Height Feet Draft Hood 8 6 8 10 15 20 30 50 100 Input Btuh Rise Vent Connector Diameter in inches 315 000 1 Ft 10 10 10 10 10 10 305 000 2 Ft 10 10 10 10 10...

Страница 13: ...tank which may be used in conjunction with this appliance shall also be installed with a properly sized rated and approved combination temperature ANSI and pressure ASME relief valve s WARNING THE PU...

Страница 14: ...F THE GAS SUPPLY SYSTEM NOT THE HEATER VENT BLOCKAGE MAY OCCUR DURING ICE STORMS IT IS IMPORTANT TO GUARD AGAINST GAS VALVE FOULING FROM CONTAMINANTS IN THE GAS WAYS SUCH FOULING MAY CAUSE IMPROPER OP...

Страница 15: ...UPPLY PRESSURE TESTING EXCEEDING 1 2 PSIG 3 5 kPa GAS SUPPLY LINE MUST BE CAPPED WHEN DISCONNECTED FROM THE HEATER FOR TEST PRESSURES OF 1 2 PSIG 3 5 kPa OR LESS THE APPLIANCE NEED NOT BE DISCONNECTED...

Страница 16: ...ULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROLWARNING ON PAGE 27 IF HIGHER PREHEATTEMPERATURESARE NECESSARY TO OBTAINADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR...

Страница 17: ...T BE CLOSED ON DURING THERINSEOPERATIONANDOPEN OFF WHENDISHWASHER IS NOT OPERATING OR WHEN ON LONG STANDBY NOTE 2 INSTALL LINE TEMPERATURE CONTROL IN AN UNINSULATED TEE BEYOND THE DISHWASHING MACHINE...

Страница 18: ...n the installation diagrams on the following pages are typical TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUILDING RECIRCULATION The discharge opening of the tempera...

Страница 19: ...3 ADJUST PLUG COCK SO THE SANITIZING LOOP FLOW RATE DOES NOT CAUSE UNNECESSARY TURBULENCE IN THE TANK PIPE RELIEF VALVE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES CIRCULATING RETURN LINE CO...

Страница 20: ...WITH MIXING VALVE TWO PRE HEATERS WITH BOOSTER HEATER DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 27 IF HIGHER PREHEAT T...

Страница 21: ...TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES PIPE RELIEF VALVE TO OPEN DRAIN IF BUILDING CIRCULATING LOOP IS USED CONNECT TO...

Страница 22: ...uctions MULTIPLE UNIT INSTALLATIONS For multiple unit installations contact Lochinvar Parts Department 300 Maddox Simpson Pkwy Lebanon TN 37090 Phone 615 889 8900 Fax 615 882 2918 email parts_team loc...

Страница 23: ...AVOIDRISKOF FIRE OR EXPLOSION PURGE DISCHARGE MUST NOT ENTER CONFINEDAREAS OR SPACES WHERE IGNITION CAN OCCUR THEAREAMUSTBE WELLVENTILATEDANDALLSOURCES OF IGNITION MUST BE INACTIVATED OR REMOVED WARNI...

Страница 24: ...24 FOR NATURAL GAS MODELS FOR YOUR SAFETY READ BEFORE OPERATING OPERATING INSTRUCTIONS FOR YOUR SAFETY READ BEFORE OPERATING...

Страница 25: ...25 FOR PROPANE GAS MODELS FOR YOUR SAFETY READ BEFORE OPERATING OPERATING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCE...

Страница 26: ...hority The water temperature is controlled by a thermostat Fig 3 which has two sensing elements One sensor is located near the top of the tank and the other is near the center The thermostat is set in...

Страница 27: ...combustion PREVENTIVE MAINTENANCE CHECK THE PILOT At least once a year check the pilot burner fig 15 and the main burner fig 16 for proper operation Refer to the following pilot and main burner sectio...

Страница 28: ...a pressure gauge or a manometer to the gauge port and refer to Table 5 for correct manifold pressure 2 Use this formula to clock the meter Be sure that other gas consuming appliances are not operating...

Страница 29: ...ther information contact your dealer ANODE ROD INSPECTION The heater tank is equipped with anode rods to provide corrosion control At least once a year the anode rods should be checked to determine if...

Страница 30: ...g screws securely 7 Replace outer jacket cover plate In some water areas the sediment might not be removed by this method and may result in the water heater making rumbling or boiling noises To dissol...

Страница 31: ...xt trial for ignition check gas supply pilot burner spark and flame sense wiring flame rod contaminated or out of position burner ground connection 3 Recycle Flame failed during run Initiate new trial...

Страница 32: ...n fuse or circuit breaker 5 Disconnect switch off 6 Harness not plugged into appliance receptacle A FLUE DAMPER OPEN OR OPENING Unit is calling for heat and damper disc should be in vertical position...

Страница 33: ...s slower Call service agent Check gas input If incorrect adjust gas pressure or replace main burner orifice Draft hood not installed or Call service agent Install draft hood or baffles as one or more...

Страница 34: ...so installed at the heater s and operational at all times The temperature and pressure relief valve installed on the heater is not an acceptable method 4 SERVICE AND REPAIR EXPENSES Under the limited...

Страница 35: ...35 NOTES...

Страница 36: ...36 Copyright 2011 Lochinvar LLC All rights reserved 300 Maddox Simpson Parkway Lebanon TN 37090 Phone 615 889 8900 Fax 615 547 1000 Technical Service email 2tech lochinvar com www Lochinvar com...

Отзывы: