background image

13

If a water heater is installed in a closed water system, contact 

the water supplier or local plumbing inspector on how to control 

this situation.

WATER (POTABLE) HEATING AND 

SPACE HEATING 

1.  All piping components connected to this unit for space heating 

applications shall be suitable for use with potable water.

2.  Toxic chemicals, such as those used for boiler treatment, shall 

NEVER be introduced into this system.

3.  This unit may NEVER be connected to any existing heating

  system or component(s) previously used with a non-potable

  water heating appliance.

4.  When  the  system  requires  water  for  space  heating  at 

temperatures higher than required for domestic water purposes, 

a tempering valve must be installed.  Please refer to installation 

diagrams on pages 16 through 21 in this manual for suggested 

piping arrangements.

5.  These  water  heaters  cannot  be  used  in  space  heating 

applications only.

 CAUTION

A  closed  system  will  exist  if  a  check  valve  (without  bypass), 

pressure reducing valve (without bypass), or a water meter (without 

bypass) is installed in the cold water line between the water heater 

and street main (or well).

Excessive pressure may develop in such closed systems, causing 

premature tank failure or intermittent relief valve operation.  

This 

is not a warranty failure.  An expansion tank or a similar device 

may be required in the inlet supply line between the appliance 

and the meter or valve to compensate for the thermal expansion 

of the water.

SYSTEM CONNECTIONS

The system installation must conform to these instructions and to 

the local code authority having jurisdiction.  Good practice requires 

that all heavy piping be supported.

THERMOMETERS (Not Supplied)

Thermometers should be obtained and field installed as shown in 

the installation diagrams.

Thermometers are installed in the system as a means of detecting 

the temperature of the outlet water supply.

RELIEF VALVE

This water heater is equipped with a combination temperature-

pressure  relief  valve  that  complies  with  the  standard  for  relief 

valves for hot water supply system, ANSI Z21.22-CSA 4.4. 

FOR 

SAFE  OPERATION  OF THE  WATER  HEATER, THE  RELIEF 

VALVE(S) MUST NOT BE REMOVED OR PLUGGED.

ASME ratings cover pressure relief capacities. ANSI ratings cover 

release rate with temperature actuation.

In addition to the appliance relief valve, each remote storage tank 

which may be used in conjunction with this appliance shall also be 

installed with a properly sized, rated and approved combination 

temperature (ANSI) and pressure (ASME) relief valve(s).

 

WARNING

THE PURPOSE OF RELIEF VALVE IS TO AVOID EXCESSIVE 

PRESSURE OR TEMPERATURE INTO THE STEAM RANGE, 

WHICH  MAY  CAUSE  SCALDING  AT  FIXTURES,  TANK 

EXPLOSION, SYSTEM OR HEATER DAMAGE.  NO VALVE IS 

TO BE PLACED BETWEEN THE RELIEF VALVE AND TANK.

Your  local  code  authority  may  have  other  specific  relief  valve

 

requirements.

A DRAIN LINE MUST BE CONNECTED TO THE RELIEF 

VALVE TO DIRECT DISCHARGE TO A SAFE LOCATION TO 

AVOID SCALDING OR WATER DAMAGE.  THIS LINE MUST 

NOT BE REDUCED FROM THE SIZE OF THE VALVE OUTLET 

AND MUST NOT CONTAIN VALVES, RESTRICTIONS NOR 

SHOULD IT BE LOCATED IN FREEZING AREAS.  DO NOT 

THREAD OR CAP THE END OF THIS LINE.  RESTRICTED 

OR BLOCKED DISCHARGE WILL DEFEAT THE PURPOSE 

OF THE VALVE AND IS UNSAFE.  DISCHARGE LINE SHALL 

BE INSTALLED TO ALLOW COMPLETE DRAINAGE OF BOTH 

THE VALVE AND LINE.

See  SERVICE  INFORMATION  section  for  procedure  and

 

precautions.

GAS PIPING

Contact your local gas service company to ensure that adequate 

gas service is available and to review applicable installation codes 

for your area.

Size the main gas line in accordance with Table 4.  The figures shown 

are for straight lengths of pipe at 0.5 in. W.C. pressure drop, which 

is considered normal for low pressure systems.  

Note:

 

 Fittings 

such as elbows, tees and line regulators will add to the pipe 

pressure drop.  Also refer to the current edition of the National 

Fuel Gas Code. For Canadian installations consult Natural Gas 

and Propane Installation Code CAN/CSA-B149.1.

TABLE 4 - GAS SUPPLY LINE SIZES (IN INCHES)*

MAXIMUM CAPACITY OF PIPE IN 

CUBIC FEET PER HOUR

 

LENGTH                    NOMINAL IRON PIPE SIZES (INCHES)

 

IN

 

FEET

 

1/2”  3/4”  1”  1 1/4”  1 1/2”  2”  2 1/2”  3” 

4”

 

10

 

175  360  680  1400  2100  3960  6300  11000  23000

 

20

 

120  250  465  950  1460  2750  4360  7700  15800

 

30

  97  200 375 770  1180 2200 3520 6250 12800

 

40

  82  170 320 660  990 1900 3000 5300 10900

 

50

 

73  151  285  580 

900  1680  2650  4750  9700

 

60

 

66  138  260  530 

810  1520  2400  4300  8800

 

70

 

61  125  240  490 

750  1400  2250  3900  8100

 

80

 

57  118  220  460 

690  1300  2050  3700  7500

 

90

 

53  110  205  430 

650  1220  1950  3450  7200

 

100

 

50  103  195  400 

620  1150  1850  3250  6700

 

125

 

44 

93  175  360 

550  1020  1650  2950  6000

 

150

 

40 

84  160  325 

500  950  1500  2650  5500

 

175

 

37 

77  145  300 

460  850  1370  2450  5000

 

200

 

35 

72  135  280 

430  800  1280  2280  4600

 WARNING

THE HEATER IS NOT INTENDED FOR OPERATION AT HIGHER 

THAN  14.0”  W.C.(3.5  kPa)  (1/2  POUND  PER  SQUARE  INCH 

Содержание CG 120 THRU 400A

Страница 1: ...E CAUTION TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION RELATIVE TO YOUR SAFETY PLEASE READ THOROUGHLY BEFORE INSTALLING AND USING THIS APPLIANCE Thank you for buying this energy efficient wate...

Страница 2: ...58 kW Hr 379 L 183 cm 12 cm 165 cm 142 cm 50 cm 58 cm 1 2 143 cm 15 cm 77 cm 1 50 2 00 2 00 1 50 2 00 2 00 286 Kg 329 Kg CG N L 250 000 BTR Hr 100 Gal 72 00 4 50 65 13 55 87 19 75 23 1 2 56 38 8 30 2...

Страница 3: ...1745 1393 1162 996 871 776 697 632 583 538 500 CG N L 199 000 BTUH 100 Gal 80 643 482 386 322 276 241 214 193 175 161 148 132 199100 A 58 Kw Hr 379 L 2434 1825 1461 1219 1045 912 810 731 662 609 560...

Страница 4: ...bleshooting Guide 32 Operational Checklist 33 Limited Warranty 34 Page Page FOREWORD These designs comply withANSI Z21 10 3 CSA4 3 as an automatic circulating or automatic storage tank type water heat...

Страница 5: ...ve and heavier than air It collects first in the low areas making its odor difficult to detect at nose level If LP gas is present or even suspected do not attempt to find the cause yourself Go to a ne...

Страница 6: ...nt with orifices sized for the particular installation elevation Correct orifice sizing and parts may be obtained from Lochinvar LLC When ordering be sure to state the model number and the altitude of...

Страница 7: ...TION and HOLD OPEN DAMPER For normal operation the switch should be in the AUTOMATIC OPERATION position If there is a problem with the damper the Service Switch can be placed in the HOLD OPEN DAMPER p...

Страница 8: ...n on combustible flooring in an alcove when the minimum clearance from any combustion construction are followed as indicated in figure 6 and Table 2 The National Sanitation Foundation also recommends...

Страница 9: ...ee MAINTENANCE section for details of tank cleanout procedure AIR REQUIREMENTS REFER TO THE CURRENT EDITION OF THE NATIONAL FUEL GAS CODE ANSI Z223 1 NFPA 54 FOR CANADA CONSULT NATURAL GAS AND PROPANE...

Страница 10: ...AND ASPHYXIATION Heater must be protected from freezing downdrafts Remove all soot or other obstructions from the chimney that will retard a free draft Type B venting is recommended with these heater...

Страница 11: ...CG N L 180080 200080 200100 199100 Input 180 000 190 000 199 000 Btuh Total Vent Height Feet Draft Hood 6 6 8 10 15 20 30 50 100 Input Btuh Rise Vent Connector Diameter in inches 180 000 1 Ft 8 8 8 8...

Страница 12: ...N L 305065 A Input 305 000 Btuh Total Vent Height Feet Draft Hood 8 6 8 10 15 20 30 50 100 Input Btuh Rise Vent Connector Diameter in inches 315 000 1 Ft 10 10 10 10 10 10 305 000 2 Ft 10 10 10 10 10...

Страница 13: ...tank which may be used in conjunction with this appliance shall also be installed with a properly sized rated and approved combination temperature ANSI and pressure ASME relief valve s WARNING THE PU...

Страница 14: ...F THE GAS SUPPLY SYSTEM NOT THE HEATER VENT BLOCKAGE MAY OCCUR DURING ICE STORMS IT IS IMPORTANT TO GUARD AGAINST GAS VALVE FOULING FROM CONTAMINANTS IN THE GAS WAYS SUCH FOULING MAY CAUSE IMPROPER OP...

Страница 15: ...UPPLY PRESSURE TESTING EXCEEDING 1 2 PSIG 3 5 kPa GAS SUPPLY LINE MUST BE CAPPED WHEN DISCONNECTED FROM THE HEATER FOR TEST PRESSURES OF 1 2 PSIG 3 5 kPa OR LESS THE APPLIANCE NEED NOT BE DISCONNECTED...

Страница 16: ...ULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROLWARNING ON PAGE 27 IF HIGHER PREHEATTEMPERATURESARE NECESSARY TO OBTAINADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR...

Страница 17: ...T BE CLOSED ON DURING THERINSEOPERATIONANDOPEN OFF WHENDISHWASHER IS NOT OPERATING OR WHEN ON LONG STANDBY NOTE 2 INSTALL LINE TEMPERATURE CONTROL IN AN UNINSULATED TEE BEYOND THE DISHWASHING MACHINE...

Страница 18: ...n the installation diagrams on the following pages are typical TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUILDING RECIRCULATION The discharge opening of the tempera...

Страница 19: ...3 ADJUST PLUG COCK SO THE SANITIZING LOOP FLOW RATE DOES NOT CAUSE UNNECESSARY TURBULENCE IN THE TANK PIPE RELIEF VALVE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES CIRCULATING RETURN LINE CO...

Страница 20: ...WITH MIXING VALVE TWO PRE HEATERS WITH BOOSTER HEATER DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 27 IF HIGHER PREHEAT T...

Страница 21: ...TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES PIPE RELIEF VALVE TO OPEN DRAIN IF BUILDING CIRCULATING LOOP IS USED CONNECT TO...

Страница 22: ...uctions MULTIPLE UNIT INSTALLATIONS For multiple unit installations contact Lochinvar Parts Department 300 Maddox Simpson Pkwy Lebanon TN 37090 Phone 615 889 8900 Fax 615 882 2918 email parts_team loc...

Страница 23: ...AVOIDRISKOF FIRE OR EXPLOSION PURGE DISCHARGE MUST NOT ENTER CONFINEDAREAS OR SPACES WHERE IGNITION CAN OCCUR THEAREAMUSTBE WELLVENTILATEDANDALLSOURCES OF IGNITION MUST BE INACTIVATED OR REMOVED WARNI...

Страница 24: ...24 FOR NATURAL GAS MODELS FOR YOUR SAFETY READ BEFORE OPERATING OPERATING INSTRUCTIONS FOR YOUR SAFETY READ BEFORE OPERATING...

Страница 25: ...25 FOR PROPANE GAS MODELS FOR YOUR SAFETY READ BEFORE OPERATING OPERATING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCE...

Страница 26: ...hority The water temperature is controlled by a thermostat Fig 3 which has two sensing elements One sensor is located near the top of the tank and the other is near the center The thermostat is set in...

Страница 27: ...combustion PREVENTIVE MAINTENANCE CHECK THE PILOT At least once a year check the pilot burner fig 15 and the main burner fig 16 for proper operation Refer to the following pilot and main burner sectio...

Страница 28: ...a pressure gauge or a manometer to the gauge port and refer to Table 5 for correct manifold pressure 2 Use this formula to clock the meter Be sure that other gas consuming appliances are not operating...

Страница 29: ...ther information contact your dealer ANODE ROD INSPECTION The heater tank is equipped with anode rods to provide corrosion control At least once a year the anode rods should be checked to determine if...

Страница 30: ...g screws securely 7 Replace outer jacket cover plate In some water areas the sediment might not be removed by this method and may result in the water heater making rumbling or boiling noises To dissol...

Страница 31: ...xt trial for ignition check gas supply pilot burner spark and flame sense wiring flame rod contaminated or out of position burner ground connection 3 Recycle Flame failed during run Initiate new trial...

Страница 32: ...n fuse or circuit breaker 5 Disconnect switch off 6 Harness not plugged into appliance receptacle A FLUE DAMPER OPEN OR OPENING Unit is calling for heat and damper disc should be in vertical position...

Страница 33: ...s slower Call service agent Check gas input If incorrect adjust gas pressure or replace main burner orifice Draft hood not installed or Call service agent Install draft hood or baffles as one or more...

Страница 34: ...so installed at the heater s and operational at all times The temperature and pressure relief valve installed on the heater is not an acceptable method 4 SERVICE AND REPAIR EXPENSES Under the limited...

Страница 35: ...35 NOTES...

Страница 36: ...36 Copyright 2011 Lochinvar LLC All rights reserved 300 Maddox Simpson Parkway Lebanon TN 37090 Phone 615 889 8900 Fax 615 547 1000 Technical Service email 2tech lochinvar com www Lochinvar com...

Отзывы: