background image

26

ADJUSTMENTS

ON INITIAL STARTUP SOME ADJUSTMENTS ARE NECESSARY.

1.  CHECK MANIFOLD AND INLET GAS PRESSURES.

2. 

TO ADJUST  PILOT  FLAME  -  FOLLOW  “PILOT  BURNER” 

PROCEDURE UNDER “PREVENTIVE MAINTENANCE”.

WATER TEMPERATURE CONTROL

 WARNING

THIS WATER HEATER IS EQUIPPED WITH AN ADJUSTABLE 

THERMOSTAT TO CONTROL WATER TEMPERATURE. HOT 

WATER  TEMPERATURES  REQUIRED  FOR  AUTOMATIC 

DISHWASHER AND LAUNDRY USE CAN CAUSE SCALD BURNS 

RESULTING IN SERIOUS PERSONAL INJURY AND/OR DEATH. 

THE TEMPERATURE AT WHICH INJURY OCCURS VARIES WITH 

THE PERSON’S AGE AND TIME OF EXPOSURE. THE SLOWER 

RESPONSE TIME OF CHILDREN, AGED OR DISABLED PERSONS 

INCREASES THE HAZARDS TO THEM. NEVER ALLOW SMALL 

CHILDREN TO USE A HOT WATER TAP, OR DRAW THEIR OWN 

BATH WATER. NEVER LEAVE A CHILD OR DISABLED PERSON 

UNATTENDED IN A BATHTUB OR SHOWER.

THE  WATER  HEATER  SHOULD  BE  LOCATED  IN AN AREA 

WHERE THE GENERAL PUBLIC DOES NOT HAVE ACCESS 

TO SET TEMPERATURES.

SETTING THE WATER HEATER TEMPERATURE AT 120°F WILL 

REDUCE THE RISK OF SCALDS.

  Some states or provinces 

require settings at specific lower temperatures.

Below you will find listed the approximate time-of-burn relationship 

for normal adult skin.  Short repeated heating cycles caused by 

small hot water uses can cause temperatures at the point of use 

to exceed the thermostat setting by up to 20°F (11°C).

If you experience this type of use, you should consider using lower 

temperature settings to reduce scald hazards.

TABLE 7

 

Water  Time to Produce 2nd & 3rd

 

Temperature  Degree Burns on Adult Skin

 

180°F (82°C)  Nearly Instantaneous

 

170°F (77°C)  Nearly Instantaneous

 

160°F (71°C)  About 1/2 Second

 

150°F (65°C)  About 1 - 1/2 Seconds

 

140°F (60°C)  Less than 5 Seconds

 

130°F (54°C)  About 30 Seconds

 

120°F (49°C)  More than 5 Minutes

Valves for reducing point-of-use temperature by mixing cold and 

hot water are available.  Also available are inexpensive devices 

that attach to faucets to limit hot water temperatures.  Contact a 

licensed plumber or the local plumbing authority.

The water temperature is controlled by a thermostat, Fig. 3, which

 

has two sensing elements.  One sensor is located near the top of 
the tank and the other is near the center.  The thermostat is set in 
the lowest position before the heater leaves the factory.

The  thermostat  temperature  dial,  Fig.  3,  is  accessible  by 

removing the control cover.  The dial is adjustable and may be 

set for 120°F (49°C) to 180°F (82°C) water temperature, but 

120°F (49°C) is the recommended starting point.  It is suggested 

the  dial  be  placed  on  the  lowest  setting  which  produces  an 

acceptable  hot  water  supply.  This  will  always  give  the  most 

energy efficient operation.  The temperature control has a 4°F 

fixed differential.

TESTING DAMPER OPERATION

With the Service Switch in the AUTOMATIC OPERATION position,

 

check the operation of the flue damper three (3) times with the 

water operating controls for proper operating sequence:

•  The damper disc must be open (in the vertical position) before 

the ignition and combustion process begins.

•  The damper disc must be in the open position when the main 

burner is firing.

•  The  gas  valve  must  close  and  the  main  burner  must  have 

ceased firing before the damper disc begins its return to the 

closed (horizontal) position.

If  during  testing  of  the  operation  of  the  damper  you  find  that 

there

 is a problem with the operation of the water heater when 

the Service Switch is in the AUTOMATIC OPERATION position: 

Reset the Service Switch to the HOLD OPEN DAMPER position 

and check operation again.

If the water heater does operate when placed in the HOLD OPEN

 

DAMPER position:

•  Refer to the EFFIKAL RVGP-FSF-SERIES TROUBLESHOOTING 

GUIDE at the end of this manual.

 CAUTION

Do not force the damper disc manually or motor damage will 

occur.

If the water heater does not operate with the Service Switch in

 

either position:

•  Refer  to  the  Troubleshooting  Sections  and  Operational

 

Checklist sections.

CHECKING VENTING

The  following  steps  shall  be  followed  with  each  appliance

 

connected to the venting system placed in operation, while any 

other  appliances  connected  to  the  venting  system  are  not  in 

operation.

1.  Seal any unused openings in the venting system.

Содержание CG 120 THRU 400A

Страница 1: ...E CAUTION TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION RELATIVE TO YOUR SAFETY PLEASE READ THOROUGHLY BEFORE INSTALLING AND USING THIS APPLIANCE Thank you for buying this energy efficient wate...

Страница 2: ...58 kW Hr 379 L 183 cm 12 cm 165 cm 142 cm 50 cm 58 cm 1 2 143 cm 15 cm 77 cm 1 50 2 00 2 00 1 50 2 00 2 00 286 Kg 329 Kg CG N L 250 000 BTR Hr 100 Gal 72 00 4 50 65 13 55 87 19 75 23 1 2 56 38 8 30 2...

Страница 3: ...1745 1393 1162 996 871 776 697 632 583 538 500 CG N L 199 000 BTUH 100 Gal 80 643 482 386 322 276 241 214 193 175 161 148 132 199100 A 58 Kw Hr 379 L 2434 1825 1461 1219 1045 912 810 731 662 609 560...

Страница 4: ...bleshooting Guide 32 Operational Checklist 33 Limited Warranty 34 Page Page FOREWORD These designs comply withANSI Z21 10 3 CSA4 3 as an automatic circulating or automatic storage tank type water heat...

Страница 5: ...ve and heavier than air It collects first in the low areas making its odor difficult to detect at nose level If LP gas is present or even suspected do not attempt to find the cause yourself Go to a ne...

Страница 6: ...nt with orifices sized for the particular installation elevation Correct orifice sizing and parts may be obtained from Lochinvar LLC When ordering be sure to state the model number and the altitude of...

Страница 7: ...TION and HOLD OPEN DAMPER For normal operation the switch should be in the AUTOMATIC OPERATION position If there is a problem with the damper the Service Switch can be placed in the HOLD OPEN DAMPER p...

Страница 8: ...n on combustible flooring in an alcove when the minimum clearance from any combustion construction are followed as indicated in figure 6 and Table 2 The National Sanitation Foundation also recommends...

Страница 9: ...ee MAINTENANCE section for details of tank cleanout procedure AIR REQUIREMENTS REFER TO THE CURRENT EDITION OF THE NATIONAL FUEL GAS CODE ANSI Z223 1 NFPA 54 FOR CANADA CONSULT NATURAL GAS AND PROPANE...

Страница 10: ...AND ASPHYXIATION Heater must be protected from freezing downdrafts Remove all soot or other obstructions from the chimney that will retard a free draft Type B venting is recommended with these heater...

Страница 11: ...CG N L 180080 200080 200100 199100 Input 180 000 190 000 199 000 Btuh Total Vent Height Feet Draft Hood 6 6 8 10 15 20 30 50 100 Input Btuh Rise Vent Connector Diameter in inches 180 000 1 Ft 8 8 8 8...

Страница 12: ...N L 305065 A Input 305 000 Btuh Total Vent Height Feet Draft Hood 8 6 8 10 15 20 30 50 100 Input Btuh Rise Vent Connector Diameter in inches 315 000 1 Ft 10 10 10 10 10 10 305 000 2 Ft 10 10 10 10 10...

Страница 13: ...tank which may be used in conjunction with this appliance shall also be installed with a properly sized rated and approved combination temperature ANSI and pressure ASME relief valve s WARNING THE PU...

Страница 14: ...F THE GAS SUPPLY SYSTEM NOT THE HEATER VENT BLOCKAGE MAY OCCUR DURING ICE STORMS IT IS IMPORTANT TO GUARD AGAINST GAS VALVE FOULING FROM CONTAMINANTS IN THE GAS WAYS SUCH FOULING MAY CAUSE IMPROPER OP...

Страница 15: ...UPPLY PRESSURE TESTING EXCEEDING 1 2 PSIG 3 5 kPa GAS SUPPLY LINE MUST BE CAPPED WHEN DISCONNECTED FROM THE HEATER FOR TEST PRESSURES OF 1 2 PSIG 3 5 kPa OR LESS THE APPLIANCE NEED NOT BE DISCONNECTED...

Страница 16: ...ULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROLWARNING ON PAGE 27 IF HIGHER PREHEATTEMPERATURESARE NECESSARY TO OBTAINADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR...

Страница 17: ...T BE CLOSED ON DURING THERINSEOPERATIONANDOPEN OFF WHENDISHWASHER IS NOT OPERATING OR WHEN ON LONG STANDBY NOTE 2 INSTALL LINE TEMPERATURE CONTROL IN AN UNINSULATED TEE BEYOND THE DISHWASHING MACHINE...

Страница 18: ...n the installation diagrams on the following pages are typical TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUILDING RECIRCULATION The discharge opening of the tempera...

Страница 19: ...3 ADJUST PLUG COCK SO THE SANITIZING LOOP FLOW RATE DOES NOT CAUSE UNNECESSARY TURBULENCE IN THE TANK PIPE RELIEF VALVE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES CIRCULATING RETURN LINE CO...

Страница 20: ...WITH MIXING VALVE TWO PRE HEATERS WITH BOOSTER HEATER DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 27 IF HIGHER PREHEAT T...

Страница 21: ...TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES PIPE RELIEF VALVE TO OPEN DRAIN IF BUILDING CIRCULATING LOOP IS USED CONNECT TO...

Страница 22: ...uctions MULTIPLE UNIT INSTALLATIONS For multiple unit installations contact Lochinvar Parts Department 300 Maddox Simpson Pkwy Lebanon TN 37090 Phone 615 889 8900 Fax 615 882 2918 email parts_team loc...

Страница 23: ...AVOIDRISKOF FIRE OR EXPLOSION PURGE DISCHARGE MUST NOT ENTER CONFINEDAREAS OR SPACES WHERE IGNITION CAN OCCUR THEAREAMUSTBE WELLVENTILATEDANDALLSOURCES OF IGNITION MUST BE INACTIVATED OR REMOVED WARNI...

Страница 24: ...24 FOR NATURAL GAS MODELS FOR YOUR SAFETY READ BEFORE OPERATING OPERATING INSTRUCTIONS FOR YOUR SAFETY READ BEFORE OPERATING...

Страница 25: ...25 FOR PROPANE GAS MODELS FOR YOUR SAFETY READ BEFORE OPERATING OPERATING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCE...

Страница 26: ...hority The water temperature is controlled by a thermostat Fig 3 which has two sensing elements One sensor is located near the top of the tank and the other is near the center The thermostat is set in...

Страница 27: ...combustion PREVENTIVE MAINTENANCE CHECK THE PILOT At least once a year check the pilot burner fig 15 and the main burner fig 16 for proper operation Refer to the following pilot and main burner sectio...

Страница 28: ...a pressure gauge or a manometer to the gauge port and refer to Table 5 for correct manifold pressure 2 Use this formula to clock the meter Be sure that other gas consuming appliances are not operating...

Страница 29: ...ther information contact your dealer ANODE ROD INSPECTION The heater tank is equipped with anode rods to provide corrosion control At least once a year the anode rods should be checked to determine if...

Страница 30: ...g screws securely 7 Replace outer jacket cover plate In some water areas the sediment might not be removed by this method and may result in the water heater making rumbling or boiling noises To dissol...

Страница 31: ...xt trial for ignition check gas supply pilot burner spark and flame sense wiring flame rod contaminated or out of position burner ground connection 3 Recycle Flame failed during run Initiate new trial...

Страница 32: ...n fuse or circuit breaker 5 Disconnect switch off 6 Harness not plugged into appliance receptacle A FLUE DAMPER OPEN OR OPENING Unit is calling for heat and damper disc should be in vertical position...

Страница 33: ...s slower Call service agent Check gas input If incorrect adjust gas pressure or replace main burner orifice Draft hood not installed or Call service agent Install draft hood or baffles as one or more...

Страница 34: ...so installed at the heater s and operational at all times The temperature and pressure relief valve installed on the heater is not an acceptable method 4 SERVICE AND REPAIR EXPENSES Under the limited...

Страница 35: ...35 NOTES...