L
i
n
M
o
t
Motion Control SW
0086h
User Err: Motion Cmd In
Wrong St
User error: The PLC program has sent a motion
command while the drive was not in an appropriate
operational state. Most of the motion commands are
accepted only in operational state 8 (Operation
Enabled).
Recommended actions: check the PLC program
0087h
User Err:
Limit Switch In High
User error: The motor moved into the Limit Switch In
while it was still in the stroke range.
Recommended actions: check the PLC program or
check homing
0088h
User Err:
Limit Switch Out High
User error: The motor moved into the Limit Switch Out
while it was still in the stroke range.
Recommended actions: check the PLC program or
check homing
0089h
User Err:
Curve Amp Scale Error
User error: The automatic calculated amplitude scale is
out of range -2000percent to 2000percent.
Recommended actions: check the PLC program or use
other curve
008Ah
User Err:
Cmd Tab Entry Not Def
Called command Table entry is not defined.
Recommended actions: check the PLC program or
define Command Table Entry.
Page 90/91
User Manual Motion Control SW / 06/12/2013
NTI AG / LinMot