ovER vIEW
WH45P
6
/42
rev 20-10
EI 180 S
(500 Pa)
EI 120 S
(500 Pa)
EI 90 S
(500 Pa)
EI 60 S
(500 Pa)
EI 30 S
(500 Pa)
Floor
EI 90 S Installation within floor p. 23
Floor minimum thickness 100 mm
Floor minimum density 650 kg/m³
Mortar sealing
ho (i
↔
o)
W
-
-
Ø
min 200
max 800
Ø
min 200
max 800
Ø
min 200
max 800
EI 120 S Installation within floor p. 23
Floor minimum thickness 150 mm
Floor minimum density 650 kg/m³
Mortar sealing
ho (i
↔
o)
W
-
Ø
min 200
max 800
Ø
min 200
max 800
Ø
min 200
max 800
Ø
min 200
max 800
EI 180 S Installation within floor p. 23
Floor minimum thickness 150 mm
Floor minimum density 2200 kg/m³
Mortar sealing
ho (i
↔
o)
W
Ø
min 200
max 800
Ø
min 200
max 800
Ø
min 200
max 800
Ø
min 200
max 800
Ø
min 200
max 800
Ø is the minimum and maximum nominal diameter of fire dampers in mm
ve
Vertical installation
ho
Horizontal installation
(i
↔
o) Origin of fire irrelevant
Pa
Pascal of depression
E Integrity
I
Thermal insulation
S
Smoke seal
W
Wet method sealing
D
Dry method sealing
Cert. N° 1812-CPR-1107
1.8.1.
Fire Batt (Weichschott) sealings
EI 120 S
(300 Pa)
EI 90 S
(300 Pa)
EI 60 S
(300 Pa)
EI 30 S
(300 Pa)
Rigid w
all
EI 120 S Installation within vertical rigid wall with Fire Batt (Weichschott) sealing p. 24
Wall minimum thickness 100 mm
Wall rock wool minimum density 500 kg/m³
Rock wool 140 kg/m³ and endothermic varnish sealing
ve (i
↔
o)
W
Ø
min 200
max 800
Ø
min 200
max 800
Ø
min 200
max 800
Ø
min 200
max 800
Minimum distance allowed between 2 dampers
200 mm
50 mm
50 mm
50 mm
Fle
xible w
all
EI 120 S Installation within vertical light wall (plasterboard) with Fire Batt (Weichschott) sealing p. 24
Wall minimum thickness 100 mm
Wall rock wool density up to 100 kg/m³ (optional)
Rock wool density 140 kg/m³ and endothermic varnish sealing
ve (i
↔
o)
W
Ø
min 200
max 800
Ø
min 200
max 800
Ø
min 200
max 800
Ø
min 200
max 800
Minimum distance allowed between 2 dampers
200 mm
50 mm
50 mm
50 mm
EI 120 S Installation within vertical light wall (gypsum blocks wall) with Fire Batt (Weichschott) sealing p. 24
Wall minimum thickness 100 mm
Wall minimum density 995 kg/m³
Rock wool 140 kg/m³ and endothermic varnish sealing
ve (i
↔
o)
W
Ø
min 200
max 800
Ø
min 200
max 800
Ø
min 200
max 800
Ø
min 200
max 800
Minimum distance allowed between 2 dampers
200 mm
50 mm
50 mm
50 mm
Floor
EI 90 S Installation within floor and Fire Batt (Weichschott) sealing p. 25
Floor minimum thickness 150 mm
Floor minimum density 650 kg/m³
Rock wool 140 kg/m³ and endothermic varnish sealing
ho (i
↔
o)
W
-
Ø
min 200
max 800
Ø
min 200
max 800
Ø
min 200
max 800
Minimum distance allowed between 2 dampers
-
200 mm
200 mm
200 mm
Ø is the minimum and maximum nominal diameter of fire dampers in mm
ve
Vertical installation
ho
Horizontal installation
(i
↔
o) Origin of fire irrelevant
Pa
Pascal of depression
E Integrity
I
Thermal insulation
S
Smoke seal
W
Wet method sealing
D
Dry method sealing
Cert. N° 1812-CPR-1107
WH45P
6
We reserve the right to make changes without prior notice