ovER vIEW
WH45P
5
/42
rev 20-10
1.7.
Performances
Performance
Reference standard
Class
Thermal fuse testing
ISO 10294-4
Compliant
Open and Close cycle reliability
EN 15650
Compliant
Resistance to corrosion in humid and saline environments
EN 60068-2-52
Degree of severity 2
Casing tightness
EN 1751
Class
C
(1)
Blade seal
EN 1751
Class 2 minimum
(1)
Casing leakage class C for diameter bigger than 315 mm as per EN 1751.
Casing leakage class B minimum for diameter less than or equal to 315 mm as per EN 1751 (class C on request).
1.8.
Fire resistance classification according to EN 13501-3-2009
EI 180 S
(500 Pa)
EI 120 S
(500 Pa)
EI 90 S
(500 Pa)
EI 60 S
(500 Pa)
EI 30 S
(500 Pa)
Rigid w
all
EI 90 S Installation within vertical rigid wall p. 19
Wall minimum thickness 100 mm
Wall minimum density 500 kg/m³
Plasterboard and rock wool 100 kg/m³ sealing
ve (i
↔
o)
D
-
-
Ø
min 200
max 800
Ø
min 200
max 800
Ø
min 200
max 800
EI 120 S Installation within vertical rigid wall p. 19
Wall minimum thickness 100 mm
Wall minimum density 500 kg/m³
Mortar or plaster putty sealing
ve (i
↔
o)
W
-
Ø
min 200
max 800
Ø
min 200
max 800
Ø
min 200
max 800
Ø
min 200
max 800
EI 180 S Installation within vertical rigid wall p. 19
Wall minimum thickness 150 mm
Wall minimum density 500 kg/m³
Mortar sealing
ve (i
↔
o)
W
Ø
min 200
max 800
Ø
min 200
max 800
Ø
min 200
max 800
Ø
min 200
max 800
Ø
min 200
max 800
Fle
xible w
all
EI 90 S Installation within vertical light wall (plasterboard) p. 21
Wall minimum thickness 100 mm
Wall rock wool density up to 100 kg/m³ (optional)
Plasterboard and rock wool 100 kg/m³ sealing
ve (i
↔
o)
D
-
-
Ø
min 200
max 800
Ø
min 200
max 800
Ø
min 200
max 800
EI 120 S Installation within vertical light wall (plasterboard) p. 21
Wall minimum thickness 100 mm
Wall rock wool density up to 100 kg/m³ (optional)
Mortar or plaster putty sealing
ve (i
↔
o)
W
-
Ø
min 200
max 800
Ø
min 200
max 800
Ø
min 200
max 800
Ø
min 200
max 800
EI 90 S Installation within vertical light wall (gypsum blocks wall) p. 22
Wall minimum thickness 70 mm
Wall minimum density 995 kg/m³
Plaster putty sealing
ve (i
↔
o)
W
-
-
Ø
min 200
max 800
Ø
min 200
max 800
Ø
min 200
max 800
EI 120 S Installation within vertical light wall (gypsum blocks wall) p. 22
Wall minimum thickness 100 mm
Wall minimum density 995 kg/m³
Plaster putty sealing
ve (i
↔
o)
W
-
Ø
min 200
max 800
Ø
min 200
max 800
Ø
min 200
max 800
Ø
min 200
max 800
WH45P
5