SPECIFICATIoN TExT

9.1. 

Series WH45P circular fire damper

Description

WH45P circular fire damper tested for fire resistance and 
smoke seal with 500 Pa depression (300 Pa for Weichschott 
sealing installations) as per EN 1366-2, classified according 
to EN 13501-3 and CE marked according to European Re-
gulation UE 305/2011 and EN 15650 standard.
Allows maximum safety for fire protection inside buildings 
providing perfect heat insulation and cold and hot smokes 
tightness. Can be connected to fire protection alarm sy-
stem or smokes detection to anticipate blade closure be-
fore fire, prevents indirect damages caused by smokes ge-
nerated by combustion.

Technical characteristics

• 

Available diameters  from 200 to 800 mm

• 

Case made from galvanized sheet steel, with a total len-
gth of 620 mm in 2 parts joined with bolts and mineral 
fiber sealing

• 

Closing mechanism built according to UNI 10365, with 
thermal fuse certified to ISo 10294-4, a test button to 
check the correct working of the damper, a release sy-
stem to block the damper in closed position and a visual 
signal "open/closed". The closing mechanism can be ea-
sily interchanged and substituted:

– 

with mechanical release and manual rearming

– 

with mechanical release and manual rearming, can be 
released remotely via a magnet and electric and signal

– 

with electric release and rearming, via and integrated 
Siemens or belimo system tested according to EN 
15650, composed by an electric thermal fuse and re-
mote controlled servomotor via an electrical signal

• 

blade damper made from calcium silicate material, com-
plete with elastomer lip gasket for the air seal of cold 
smoke, as per EN 1366-2

• 

blade axis made of steel, patented fixing on casing, with 
low friction bearings for high reliability in case of fire.

• 

Thermal, expanding graphite gasket

• 

Thermal fuse with melting point certified ISo 10294-4 at 
70 °C or 95 °C (version with mechanical release) or at 72 
°C (version with servo motor)

• 

Absence of thermal bridge between the wall of installa-
tion and the ducts before and after

• 

Resistance to salt spray, tested with severity 2, according 
to EN 60068-2-52

• 

Casing leakage class C for diameter bigger than 315 mm 
as per EN 1751.

• 

Casing leakage class b minimum for diameter less than 
or equal to 315 mm as per EN 1751 (class C on request).

Installation

• 

Installation within vertical rigid walls made from aerated 
concrete blocks, standard concrete or masonry:
with a minimum thickness of 150 mm and minimum 
density of 500 kg/m³ and mortar sealing (EI 180 S)
with a minimum thickness 100 mm and density 500 kg/
m³ and mortar or plaster putty sealing (EI 120 S)
with a minimum thickness 100 mm and density 500 kg/
m³ and plasterboard and rockwool sealing (EI 90 S)

• 

Installation within light plasterboard walls with mini-
mum thickness of 100 mm  and sealed with mortar or 
plaster putty (EI 120 S) or rock wool (EI 90 S)

• 

Installation within light walls made with gypsum blocks 
100 mm thick and minimum density 995 kg/m³ (EI 120 S) 
or minimum thickness of 70 mm and minimum density 
995 kg/m³ (EI 90 S)

• 

Installation within concrete floors with a minimum thi-
ckness of 150 mm and minimum denisty of 2200 kg/m³ 
(EI 180 S) or aerated concrete with minimum thickness 
150 mm and minimum density 650 kg/m³ (EI 120 S) or 
aerated concrete with minimum thickness 100 mm and 
minimum density 650 kg/m³ (EI 90 S)

• 

Installation with Fire batt (Weichschott) sealing within 
vertical rigid walls made from aerated concrete blocks, 
standard concrete or masonry with minimum thickness 
100 mm and minimum density 500 kg/m³, within light 
plasterboard walls with minimum thickness of 100 mm, 
within gypsum blocks light walls with with minimum 
thickness 100 mm and minimum density 995 kg/m³ (EI 
120 S)

• 

Installation with Fire batt (Weichschott) sealing within 
concrete floors or aerated concrete with minimum thi-
ckness 150 mm and minimum density 650 kg/m³ (EI 90 S)

• 

Fire resistance characteristics independent from di-
rection of the source of the fire according to EN 1366-2 
article 6.2

• 

Installation possible  with damper blade placed horizon-
tally or vertically, with the mechanism placed in left/right 
or above/below

Accessories

• 

Motorised version with 24 v or 230 v servomotor instal-
led on the damper

• 

Set of microswitches with four No/NC position detecting 
connectors for open and closed damper, as per standard 
UNI 10365

• 

Immission and interruption magnet 24 v DC or 230 v AC 
with rectifier

• 

Power supply and communication unit LonWorks, MP-
bus, Modbus, bacnet

WH45P

 

37

We reserve the right to make changes without prior notice

Содержание WH45P

Страница 1: ...FIRE DAMPER CIRCULAR SERIES WH45P 500 Pa 300 Pa Cert N 1812 CPR 1107 Technical Manual WH45P WH45P lindab we simplify construc tion Technical Manual Installation type with fire resistance class English...

Страница 2: ...This is a 42 page manual...

Страница 3: ...p 21 3 11 Installation within vertical light wall gypsum blocks wall p 22 3 12 Installations within floor p 23 3 13 Installations within vertical wall with Fire Batt Weichschott sealing p 24 3 14 Inst...

Страница 4: ...erial Lip seal on blade border for cold smoke seal Internal intumescent gasket for hot smoke seal 1 3 European Standards applied CE certification EN 15650 Test EN 1366 2 Classification EN 13501 3 Ther...

Страница 5: ...ax 800 min 200 max 800 min 200 max 800 EI 180 S Installation within vertical rigid wall p 19 Wall minimum thickness 150 mm Wall minimum density 500 kg m Mortar sealing ve i o W min 200 max 800 min 200...

Страница 6: ...x 800 min 200 max 800 min 200 max 800 Minimum distance allowed between 2 dampers 200 mm 50 mm 50 mm 50 mm Flexible wall EI 120 S Installation within vertical light wall plasterboard with Fire Batt Wei...

Страница 7: ...kwise For power supply interruption electromagnet provide power supply and pull the magnet knob before opening the fire damper In case of closed damper as a result of the action of the thermosensitive...

Страница 8: ...the damper when the motor is connected press the switch on the temperature sensor or cut off the power supply Blade opening mode Make sure that the damper is open before the ventilation system start...

Страница 9: ...0 0 0 0 35 80 Lp mm 45 45 45 45 45 45 45 Lp Overlap length between fire damper and duct 2 1 1 Manual 2 1 2 Manual with magnet 2 1 3 Siemens motorized version 2 1 4 Belimo motorized version 2 2 Weight...

Страница 10: ...from atmospheric conditions use in explosive environments use on board of ships use in cooker extraction hoods use in pneumatic conveying systems of dust or corn use in ventilation systems within loc...

Страница 11: ...case of fire It is recommended not to compress flexible connectors in the installation phase Flexible connector must be at least 100mm long and in order that possible duct thermal expansions are balan...

Страница 12: ...ion for transfer appli cation is conform to section Fire resistance classification according to EN 13501 3 2009 p 5 limited to EI 120S if the ducted classification is higher End cap with mesh shall be...

Страница 13: ...cap length mechanism side L2 End cap length mechanism opposite side 3 6 3 How to order transfer Application Code Type EPNF End cap with mesh Diameter XYZ Nominal diameter dimension mm Length XYZ Leng...

Страница 14: ...r putty sealing 50 75 EI 90 S Installation within vertical rigid wall p 19 Plasterboard and rock wool 100 kg m sealing 50 75 Flexible wall EI 120 S Installation within vertical light wall plasterboard...

Страница 15: ...rtical light wall gypsum blocks wall with Fire Batt Weichschott sealing p 24 Rock wool 140 kg m and endothermic varnish sealing 50 50 Floor EI 90 S Installation within floor and Fire Batt Weichschott...

Страница 16: ...ht plasterboard vertical walls During testing light plasterboard walls have been used with the following characteristics U shaped horizontal metal frame 50 mm and C shaped vertical frame 49 mm made fr...

Страница 17: ...ween each other vertical profile fixing with selfthreading screws or by clin ching to the bottom horizontal profile and insertion in the top horizontal profile profiles fixed using self threading scre...

Страница 18: ...damper 3 8 5 Aerated concrete floors Aerated concrete floors can be built during installation or with preformed slabs with interlocking shaped edges ac cording to the following characteristics minimu...

Страница 19: ...mper 3 9 3 Filling Fill the space between the wall and the damper as indica ted in the table and in the drawing Sealing with concrete is not allowed Fire resistance classi fication D hole size mm Damp...

Страница 20: ...see table above Lp Overlap length between fire damper and duct see section Dimension p 9 EI 120 S EI 180 S Installations within vertical rigid wall 1 Mortar M 10 EN998 2 or plaster putty D Hole size s...

Страница 21: ...per protrusion from the wall E mm Wall minimum thick ness S mm Sealing EI 90 S Installation within vertical light wall plasterboard Wall rock wool density up to 100 kg m optional EI 90 S 500 Pa Da 35...

Страница 22: ...he damper as indica ted in the table and in the drawing Sealing with concrete is not allowed Fire resistance classi fication D hole size mm Damper protrusion from the wall E mm Wall minimum thick ness...

Страница 23: ...loor and the damper as indica ted in the table and in the drawing Sealing with concrete is not allowed Fire resistance classi fication D hole size mm Damper protrusion from the floor E mm Floor minimu...

Страница 24: ...CFS S ACR minimum thickness of 1 mm Fire resistance classi fication D hole size mm Damper protrusion from the wall E mm Wall minimum thick ness S mm Sealing Rigid wall EI 120 S Installation within rig...

Страница 25: ...k wool panels with minimum thickness of 50 mm and minimum density of 140 kg m The panels must be covered on both faces of the wall with endothermic varnish type PROMASTOP E PASTE or HILTI CFS CT minim...

Страница 26: ...ition 1 NC contact of SC microswitch When the fire blade is closed the circuit is open 2 NO contact of SC microswitch When the fire blade is closed the circuit is closed 3 NC contact of SA microswitch...

Страница 27: ...d power consumption Power interrruption magnet P 4 5W 24V DC or 230V AC version Power input magnet P 4 5W 24V DC or 230V AC version Motor 24V AC DC WH45PVMB Belimo BFN24T Opening 4W In stand by 1 4W M...

Страница 28: ...ble Check damper cleanliness and clean where necessary Check the condition of blades and seals rectify and re port where necessary Check the correct opening and closing of the fire dam per by manual o...

Страница 29: ...2676 54 1 3090 58 5 355 3046 49 1 3730 55 2 4307 59 6 400 4244 50 2 5198 56 3 6002 60 7 450 5888 51 3 7211 57 4 8326 61 8 500 7891 52 2 9664 58 4 Qmax 560 10812 53 3 13242 59 4 Qmax 600 13098 53 9 Qma...

Страница 30: ...level graph 200 560 Example Diameter mm 315 mm Q Air flow m h Q 3000 m h V1 Frontal air speed m s V1 10 7 m s P Pressure drop Pa From graph P 37 7 Pa Lw Sound level dB A From graph Lw 56 dB A WH45P 3...

Страница 31: ...Pa From graph P 36 Pa Lw Sound level dB A From graph Lw 59 dB A 6 6 Sound spectrum table Correction used to estimate the octave band spectrum Values to be added to the noise levels in dB A Frontal spe...

Страница 32: ...when power is not supplied Power supply 24V DC 4 5W WHKMG024KIT Remote control magnet optional for manual command fire dampers Power supply interruption version the fire damper blade closes when power...

Страница 33: ...BFN230T BF230T Siemens motor for dampers predisposed for use with GGA126 GNA126 GRA126 24V AC DC power supply thermofuse 72 C GGA126 GNA126 GRA126 Siemens motor for dampers predisposed for use with G...

Страница 34: ...ST WHKBKN230 24LON Modbus Communication and power supply unit BKN230 24MOD for Belimo motors BFL24T ST BFN24T ST and BF24T ST WHKBKN230 24MOD Communication and power supply unit MPBUS for BKS24 9A or...

Страница 35: ...ir sealing 300 Pa for Fire Batt Weichschott installations Command type B Manual command M Manual command with magnet Position indication microswitches S0 Without position microswitches not recommended...

Страница 36: ...0 250 300 315 355 400 450 500 560 600 630 710 800 Belimo M M M M M M M M M M M G G Siemens S S S S P P P P P P P G G Belimo Siemens 24V 230V 24V 230V S GRA126 GRA326 P GNA126 GNA326 M BFN24T BFN230T G...

Страница 37: ...eter bigger than 315 mm as per EN 1751 Casing leakage class B minimum for diameter less than or equal to 315 mm as per EN 1751 class C on request Installation Installation within vertical rigid walls...

Страница 38: ...att Weichschott sealing p 25 Maintenance and inspections p 28 Updated table Electrical specifications p 27 Motorized fire dampers p 35 Electric motor driven actuators p 36 Accessories and spare parts...

Страница 39: ......

Страница 40: ......

Страница 41: ...tly improving its products the aesthetic or dimensional features the technical data the equi pment and accessories indicated could be subject to variations www lindab com Fire dampers are manufactured...

Страница 42: ...easy to use as well as offering efficient availability and logistics We are also working on ways to reduce our impact on our environment and climate We do that by developing methods to produce our sol...

Отзывы: