INSTALLATIoN
WH45P
12
/42
rev 20-10
3.6.
Transfer Application (application not connected to air ducts on one or both sides)
Note: For this application please refer to national legislation to verify if any specific obligation is required.
Following tests performed as per EN 1366-2, section 6.3.6 Standard, it is possible to install the fire damper free from air duct
from one or both sides.
•
Attention: fire resistance classification for transfer appli-
cation is conform to section Fire resistance classification
according to EN 13501-3-2009 p. 5 limited to EI 120S
if the ducted classification is higher.
•
End cap with mesh shall be mounted on the side not
connected to air duct.
•
End cap with mesh is made from galvanized steel sheet.
•
End cap with mesh is supplied not installed on the fire
damper.
•
Refer to the section How to order (transfer Applica-
tion) p. 13 for codes to use.
3.6.1.
Components (Transfer Application)
1.
End cap with mesh (to fix to fire damper with steel screws)
2.
Fire damper
WH45P
12