background image

Subject to modifications

User Manual

LMC 1

9.3EN-98001-A07

Page 6 of 36

LINCOLN GmbH • Postfach 1263 • D-69183 Walldorf • Tel +49 (6227) 33-0 • Fax +49 (6227) 33-259

Description

 

Application

 

6606m06

 

Fig. 1 

LMC 1 membrane keypad

 

1 - 

4-digit 7-segment display

 

2 - 

LED status display

 

- Power on (white) 
- Readiness for operation (green) / Malfunction (red)

 

- Pump is running (green) 
- Low-level signal (yellow)

 

3 - 

Operating panel

 

- left  MENU / RUN 
- right

 

ENTER / RESET 

- up (

UP

)

 

 

short 

+ 1

 count value

 

       

 

long + high speed

 

- down (

DOWN

)

 

short 

- 1

 count value

 

       

 

long – high speed

 

4 - 

Information on handling

 

 

 

6608m06

 

Fig. 2 

The LMC 1 control p.c.b. (VDC)

 

 

‚

 

The LMC 1 multi controller is used to control and monitor 
the following stationary Lincoln lubrication systems.

 

- Progressive systems

 

- Spray systems

 

- Two-line systems

 

- Centro-Matic

®

 systems

 

- PMA systems

 

- COBRA chain-lubrication systems

 

‚

 

It combines the flexibility of freely programmable 
controllers with the cost effectiveness of pre-programmed 
control p.c.b.’s.

 

‚

 

Functionality and menu display in the LMC 1 are set to 
specifically matching parameters depending on the 
lubrication system selected.

 

Parameter name (t = time, c = counter):

 

- t – MO  .............................. (Monitoring) Monitoring time

 

- t – PS .........................................................  Pause time

 

- t – rn  ........................................... (run) Lubrication time

 

- t – od ..................................  (off delay) Switch-off delay

 

- t – cl  .................................  (clean) Nipple cleaning time

 

- c – rn .........  (run) Lubrication / revolution / stroke count

 

- c – PS  ............................. Number of pause revolutions

 

- c – bl  ............................... (Bolts) Number of chain links

 

 

‚

 

The lubrication system and defaults for its parameters can 
be set (UP & DOWN keys, pos. 3, Fig. 1) using the DIP-
switches (SW1, SW2, SW3 & SW4, pos. 12, Fig. 2)

 

‚

 

You can make additional parameter modifications with the 
operating panel on the LMC 1 membrane keypad in the 
“Setup mode“ (see the “Operating“ section in the 
respective lubrication system.

 

‚

 

All settings and count values are saved every 30 minutes 
in the LMC 1 EEPROM, which means they are not lost 
even if the mains supply fails.

 

 
 
 
 
 
 
 
 
 
 
 
 

12 -  DIP-switch (from left: SW1, SW2, SW3, SW4)

 

Содержание LMC 1

Страница 1: ...Subject to modifications User Manual LMC 1 9 3EN 98001 A07 LINCOLN GmbH Postfach 1263 D 69183 Walldorf Tel 49 6227 33 0 Fax 49 6227 33 259 LMC 1 Lincoln Multi Controller 1 6603m07...

Страница 2: ...0 Fax 49 6227 33 259 All rights reserved Any duplication of this User Manual in its entirety or in part by whatever means is prohibited without the prior consent in writing of Lincoln GmbH Subject to...

Страница 3: ...tion of accidents 5 Operation maintenance and repair 5 Disposal 5 Description Application 6 MENU Reference list 7 Installation Connection 8 Mounting channels for fastening 36 Page Technical data 9 Rep...

Страница 4: ...of contents Procedural instruction User s Responsibility To ensure the safe operation of the unit the user is responsi ble for the following 1 The pump system shall be operated only for the in tended...

Страница 5: ...es Even during a standstill the motor or valve may be applied with voltage Accident prevention rules Comply with the rules applicable in the country of use Do not operate using non authorized spare pa...

Страница 6: ...bility of freely programmable controllers with the cost effectiveness of pre programmed control p c b s Functionality and menu display in the LMC 1 are set to specifically matching parameters dependin...

Страница 7: ...meter RUN Acknowledgement of the modifications carried out return to the operating mode ENTER MENU Centro Matic systems ENTER 2 min t MO Monitoring time 1 min to 99 min and 59 sec 1 second ENTER 10 mi...

Страница 8: ...pply 24 VDC 10 A or 230 VAC 3 A 8 Program interface RJ 45 6607m07 Fig 4 Housing Route the LMC 1 connection cables through the cable glands item 9 and 10 on the bottom of the housing Possible tensile f...

Страница 9: ...es Power failure backup time 15 ms at 230 VAC Protection class IP 54 AC input Input voltage 230 VAC 10 50 60 Hz 5 Fast fuse 4 A 250 V internal DC input Input voltage 24 VDC 20 Slow fuse 10 A Safety DI...

Страница 10: ...replace if applicable Set pause time is shorter than the lubricating time Increase the pause time As the pause time is also restarted at the start of the lubricating time the following setting value...

Страница 11: ...U with monitored metering device 1 2 SU without monitored metering device 2 3 SU with monitored metering device 2 4 3ZWV without monitored metering device 3 6663c06 0 1 0 0 Two line 5 3ZWV with monito...

Страница 12: ...6227 33 259 c rn Number of lubricating cycles 0001 c PS Number of pause cycles ENTER ENTER ENTER 0001 ENTER RUN Operating mode Configuration mode Operating mode To set parameters back or acknowledge...

Страница 13: ...g Variable Cycle dependent lubrication Number of chain pause cycles Number of chain links Connection 6617b06 Fig 6 Signal input connection A External contact 1 B Chain sensor C Low level signal D High...

Страница 14: ...Set the DIP switches see view Fig 2 page 6 as shown in Fig 8 1 1 1 0 SW1 ON SW2 ON SW3 ON SW4 OFF Select from the following versions to set the parameter defaults in your PMA lubrication system no st...

Страница 15: ...ycles Count value 1 lubricating cycle Conclude the selection with the ENTER key Continue with the c PS menu item Menu item c PS Number of pause cycles The number of pause cycles sets the number of non...

Страница 16: ...cktour t MO Monitoring time 02 00 min sec t PS Pause time ENTER ENTER t rn Lubricating time ENTER ENTER 00 10 h min 02 00 Min Sek ENTER ENTER RUN Operating mode Configuration mode Operating mode 0001...

Страница 17: ...ime or cycle dependent lubrication Monitoring time Fixed Filling time monitoring 15 min Connection 6611b06 Fig 12 Signal input connection A External contact 1 B Metering device sensor C Low level sign...

Страница 18: ...ON SW4 OFF Select from the following versions to set the parameter defaults in your progressive system no metering device and no cycle counter 0 with one metering device and no cycle counter 1 with on...

Страница 19: ...e pause time is also restarted at the start of the lubricating time the following setting value applies Pause time Lubricating time If the ratio is reversed the fault indication E PD appears in the LM...

Страница 20: ...rf Tel 49 6227 33 0 Fax 49 6227 33 259 t MO Pump runtime monitoring 12 00 min sec t PS Pause time ENTER ENTER ENTER 00 10 h min ENTER RUN Operating mode Configuration mode Operating mode To set parame...

Страница 21: ...time Fixed Filling time monitoring 15 min Connection 6615b06 Fig 18 Signal input connection A External contact 1 B Metering device sensor C Low level signal D High level signal E Pressure switch pump...

Страница 22: ...parameter defaults in your two line plant electronic change over without metering device monitoring 0 electronic change over with metering device monitoring 1 pressure controlled change over without m...

Страница 23: ...ll pulse Press the UP or DOWN key to configure the monitoring time Section 1 sec to 99 min and 59 sec Count value 1 sec Conclude the selection with the ENTER key Continue with the t PS menu item 6001a...

Страница 24: ...33 0 Fax 49 6227 33 259 Centro Matic systems Quicktour t MO Monitoring time 02 00 min sec t PS Pause time ENTER ENTER ENTER RUN Operating mode Configuration mode Operating mode To set parameters back...

Страница 25: ...ic systems Variable Pause time Monitoring time Switch off delay time Connection 6614b06 Fig 24 Signal input connection A External contact 1 B Pressure switch 1 C Low level signal D High level signal E...

Страница 26: ...he DIP switches see view Fig 2 page 6 as shown in Fig 26 1 1 1 0 SW1 ON SW2 ON SW3 ON SW4 OFF Select from the following versions to set the parameter defaults in your Centro Matic system with one pres...

Страница 27: ...he pause time determines the time interval that must expire between two lubrication sequences Press the UP or DOWN key to configure the pause time Section 1 min to 99 h and 59 min Count value 1 min Co...

Страница 28: ...leaning time 10 sec c PS Number of pause cycles ENTER ENTER ENTER 0001 ENTER RUN Operating mode Configuration mode Operating mode To set parameters back or acknowledge settings continue in operating m...

Страница 29: ...ble Nipple cleaning time Cycle dependent lubrication Number of pause cycles Number of chain links Fixed Filling time monitoring 1 min Connection 6618b06 Fig 30 Signal input connection A External conta...

Страница 30: ...beginning 6001a02 NOTE As soon as you press the UP key pos a Fig 32 outside of the configuration mode the actual rest of the expired pause cycle is shown in the display Parameter default 6001a02 NOTE...

Страница 31: ...Press the UP or DOWN key to configure the number of lubricating cycles Section 1 to 9999 lubricating cycles Count value 1 lubricating cycle Conclude the selection with the ENTER key Continue with the...

Страница 32: ...use time ENTER ENTER t rn Lubricating time ENTER ENTER 00 10 h min 02 00 min sec ENTER ENTER RUN Operating mode Configuration mode Operating mode 0001 ENTER ENTER To set parameters back or acknowledge...

Страница 33: ...or cycle dependent lubrication Monitoring time Re spraying time Fixed Filling time monitoring 15 min Connection 6616b06 Fig 35 Signal input connection A External contact 1 B Metering device sensor C...

Страница 34: ...e parameter defaults in your spray lubrication system no metering device no cycle counter clock pulsed 0 with metering device no cycle counter clock pulsed 1 with metering device and cycle counter clo...

Страница 35: ...determines how long a lubrication sequence takes to provide all the lubrication points in the spray lubrication system with sufficient lubricant Press the UP or DOWN key to configure the lubrication t...

Страница 36: ...9 Lincoln GmbH Heinrich Hertz Stra e 2 8 69190 Walldorf Germany Tel 49 6227 33 0 Fax 49 6227 33 259 Lincoln Industrial Corporation 51 Changi Business Park Central 2 09 06 The Signature Singapore 48606...

Отзывы: