Volume,
Mass,
Level1 – level from the 1st (central) beam,
Level2 – level from the 2nd beam,
Level3 – level from the 3rd beam,
Level4 – level from the 4th beam,
Level5 – level from the 5th beam.
average_level – average level,
min_level – minimum level,
max_level – maximum level.
Note: If several level transmitters are installed on the same vessel, average_level,
min_level, and max_level tags are calculated for all level transmitters (their beams)
installed on this vessel.
9.5.
Remote connection of SCADA system.
To enable connection to SCADA volume measurement system installed on a remote
computer, first install Limaco OPC Server software on this computer. Configure it
as a remote server.
To do this, make changes manually to limacopc.cfg file generated during the instal-
lation.
Replace MODBUS=YES line with MODBUS=NO line.
Next, set the direction of WCF exchange towards the server located on the host
computer:
Enter «WCF=CLIENT»
in «WCF=» line.
Then enter the line «URI=http://192.168.1.10:8000/service»
indicating the IP address or the name of computer with the host OPC-server in-
stalled and the number of port for exchange.
47
RE_ULM3DX_18_02_20
Содержание ULM-3D Series
Страница 4: ...all dimensions of ULM 3D 5 54 13 4 Handling of cable gland 56 4 RE_ULM3DX_18_02_20 ...
Страница 24: ...Fig 4 13 Installation examples 24 RE_ULM3DX_18_02_20 ...
Страница 29: ...13 Switch matching load of RS 485 line RA B 120 Ohm 29 RE_ULM3DX_18_02_20 ...
Страница 53: ...13 2 Level transmitter connection to the mount flange and overall dimensions of ULM 3D 5 53 RE_ULM3DX_18_02_20 ...
Страница 55: ...Installation of ULM 3D 1 level transmitter on a nozzle 55 RE_ULM3DX_18_02_20 ...