Chapter 6 - Troubleshooting & Maintenance
83
6.3.1
Motor Does Not RUN
No
Charge LED ON?
Yes
Inverter Trouble
Yes
Input Power ON?
RST
or
BX
Terminal OFF?
Check
RST, BX
Terminal Input
No
FUN 02
Set to 'Key'?
Yes
FUN 02 set to
'Terminal 1' or 2?
No
FUN 01
Set to 'Key'?
Check FX, RX
Terminal Input
Yes
FUN 01
Set to 'Terminal'?
No
Freq. Set
in DRV 00?
Yes
Voltage Output
at U,V,W?
Yes
Check Output Wiring
and Motor
Yes
Command freq. Higher
than FUN06?
Yes
Analog Signal
V1-5G or I-5G?
Yes
Yes
Set Commnad freq.
higher than Starting
freq. [FUN 06]
No
Iverter Trouble
Yes
* Please check if the
Run
Prevetion
is set correctly in
FUN 03