Chapter 5 - Parameter Description (I/O Group)
66
5.3
I/O Group
I/O 00: Jump to Desired Code #
I/O
¢º
Jump Code
00 1
Setting Range:
1 to 60
Factory Default:
1
Jumping directly to any program code can be
accomplished by entering the desired code number.
I/O 01 - 06: Multi-Function Inputs
(Terminals P1 ~ P6)
I/O
¢º
P1 Input
01 SPD_L
Factory Default:
SPD_L
I/O
¢º
P2 Input
02 SPD_M
Factory Default:
SPD_M
I/O
¢º
P3 Input
03 SPD_H
Factory Default:
SPD_H
I/O
¢º
P4 Input
04 ACCT_L
Factory Default:
ACCT_L
I/O
¢º
P5 Input
05 ACCT_M
Factory Default:
ACCT_M
I/O
¢º
P6 Input
06 ACCT_H
Factory Default:
ACCT_H
Multi-function input terminals can be defined for
many different applications. The following table
shows various definitions for them.
Setting Range
Description
SPD_L
SPD_M
SPD_H
Multi-Step Speed via P1~P6
JOG
Jog
ACCT_L
ACCT_M
ACCT_H
Multi-Accel/Decel Time Select
UP
Increase Drive Output Frequency
DOWN
Decrease Drive Output Frequency
HOLD
Hold Drive Output Frequency
DIS_OPT
Disable Option Control
COMM_CONN
Connect Motor to Commercial Line
EXT_DCBR
Initiate Dynamic Braking Mode
EXT_TRIP
Initiate External Fault
INTERLOCK
Used for MMC Option
SPD_L, SPD_M, SPD_H:
[Multi-Step Speed]
By setting P1, P2 and P3 terminals to ‘SPD_L’,
‘SPD_M’, and ‘SPD_H’ respectively, the inverter
can operate at the preset frequency set in [I/O 13]
through [I/O 19].
The preset frequencies are determined by the
combination of P1, P2 and P3 terminals as shown in
the following table.
Multi-Step Speed Selection Table
Speed
0
Speed
1
Speed
2
Speed
3
Speed
4
Speed
5
Speed
6
Speed
7
SPD_L
0
1
0
1
0
1
0
1
SPD_M
0
0
1
1
0
0
1
1
SPD_H
0
0
0
0
1
1
1
1
0: OFF, 1: ON
Содержание SV030iH-2U
Страница 13: ...Chapter 1 Installation 11 STARVERT iH VARIABLE FREQUENCY DRIVE STARVERT IH SV132iH 4U SV160iH 4U...
Страница 26: ...Chapter 2 Operation 24 Blank Page...
Страница 34: ...Chapter 3 Quick Start Procedures 32 Blank Page...
Страница 42: ...Chapter 4 Parameter List 40 Blank Page...
Страница 66: ...Chapter 5 Parameter Description Function Group 64...
Страница 67: ...Chapter 5 Parameter Description Function Group 65 Blank Page...
Страница 81: ...Chapter 5 Parameter Description I O Group 79 Blank Page...