Chapter 5 - Parameter Description (Drive Group)
42
DRV 05: Output Power Display
DRV
¢º
Power
05 47.8kW
Displays inverter output power (kW) when the drive
is running.
DRV 06: Fault Display
DRV
¢º
Fault
05 No Fault
Displays the status of a fault. The output of the
inverter is turned off when a fault condition occurs.
The condition at the time of the fault can be
examined (Motor Current and Output Frequency).
The Stop LED blinks when a fault has occurred. The
following table shows the fault item.
Display
Fault
Remark
OC Trip
Over Current
Latch
OV Trip
Over Voltage
Latch
EXT Trip
External Trip
Latch
BX
Inverter Disable
Unlatch
LV Trip
Low Voltage
Unlatch
Fuse Open
Fuse Blown
Latch
GF Trip
Ground Fault
Latch
Over Heat
Cooling Problem
Latch
ETH
Electronic Thermal Protected Latch
OC Limit
Over Current
Latch
M/C Fail
Magnetic Contactor Problem
Unlatch
Inv OLT
Inverter Overload
Latch
SC Trip
1
Short Through Trip
Latch
n
Note:
A latched fault must be released by the [RESET] key
or reset (RST) terminal. Unlatched faults are released upon
condition or command.
1
Available for models over 220kW. To reset this fault, the main input
power should be disconnected.
Содержание SV030iH-2U
Страница 13: ...Chapter 1 Installation 11 STARVERT iH VARIABLE FREQUENCY DRIVE STARVERT IH SV132iH 4U SV160iH 4U...
Страница 26: ...Chapter 2 Operation 24 Blank Page...
Страница 34: ...Chapter 3 Quick Start Procedures 32 Blank Page...
Страница 42: ...Chapter 4 Parameter List 40 Blank Page...
Страница 66: ...Chapter 5 Parameter Description Function Group 64...
Страница 67: ...Chapter 5 Parameter Description Function Group 65 Blank Page...
Страница 81: ...Chapter 5 Parameter Description I O Group 79 Blank Page...