Chapter 5 - Parameter Description (I/O Group)
69
[‘COMM_CONN’ Sequence]
EXT_DCBR:
DC Injection Braking can be activated, while the
inverter is stopped, by configuring one of the multi-
function input terminals to ‘EXT_DCBR’. To
activate the DC Injection Braking, close the contact
on the assigned terminal while the inverter is
stopped.
Example:
If P4 is configured as EXT_DCBR, then DC injection braking is
achieved on stop by using P4 input terminal.
[External DC-braking in stop]
EXT_TRIP:
This is a normally closed contact input. When an
input terminal is set to ‘EXT_TRIP’ and the contact
input opens, the inverter displays the fault and cuts
off its output. This can be used as an external latch
trip. The inverter will decelerate as configured in
[FUN 15]. The inverter must be RESET and the
RUN command must be re-initiated to restart the
drive.
I/O 07 - 11: Multi-function Outputs
(OC1, OC2, OC3, AUX1, AUX2)
I/O
¢º
OC1 output
07 STEP_L
Factory Default:
STEP_L
I/O
¢º
OC2 output
08 STEP_M
P4-CM
ON
Output Frequency
Time
Time
FX-CM
ON
Time
Output Voltage
Time
FUN 36
DC injection braking voltage
FX-CM
ON
Output Frequency
Time
Time
P5-CM
ON
Time
AUX1
(1A-1B)
ON
Time
M1
ON
Time
M2
ON
Time
ON
t1
t2
Inverter
Drive
Inverter
Drive
Commercial
Line Drive
t1, t2: 50msec (interlock time)
Speed Search
Содержание SV030iH-2U
Страница 13: ...Chapter 1 Installation 11 STARVERT iH VARIABLE FREQUENCY DRIVE STARVERT IH SV132iH 4U SV160iH 4U...
Страница 26: ...Chapter 2 Operation 24 Blank Page...
Страница 34: ...Chapter 3 Quick Start Procedures 32 Blank Page...
Страница 42: ...Chapter 4 Parameter List 40 Blank Page...
Страница 66: ...Chapter 5 Parameter Description Function Group 64...
Страница 67: ...Chapter 5 Parameter Description Function Group 65 Blank Page...
Страница 81: ...Chapter 5 Parameter Description I O Group 79 Blank Page...