Chapter 2 - Operation
23
2.6
Operation Method
The iH has several operation methods as shown below.
Operation Method
Function
Function Setting
Operation using
keypad
Run/Stop command and frequency are set only through
the keypad.
FUN 01: Key
FUN 02: Key
Operation using
Control
Terminals
Closing FX or RX terminal performs Run/Stop.
Frequency reference is set through V1 or I terminal.
FUN 01: Terminal
FUN 02: Terminal-1 or
Terminal-2
Run/Stop is performed by the keypad.
Frequency reference is set through the V1 or I terminal.
FUN 01: Terminal
FUN 02: Key
Operation using both
Keypad and Control
Terminals
Closing FX or RX terminal performs Run/Stop.
Frequency reference is set through the keypad.
FUN 01: Key
FUN 02: Terminal-1 or
Terminal-2
Operation using RS485 communication between
inverter and computer.
FUN 01: Remote
FUN 02: Remote
I/O 48: RS485
Operation using ModBus RTU communication between
inverter and PLC.
FUN 01: Remote
FUN 02: Remote
I/O 48: ModBus RTU
Option
Operation using FNet communication between inverter
and computer.
FUN 01: Remote
FUN 02: Remote
I/O 48: FNet
Содержание SV030iH-2U
Страница 13: ...Chapter 1 Installation 11 STARVERT iH VARIABLE FREQUENCY DRIVE STARVERT IH SV132iH 4U SV160iH 4U...
Страница 26: ...Chapter 2 Operation 24 Blank Page...
Страница 34: ...Chapter 3 Quick Start Procedures 32 Blank Page...
Страница 42: ...Chapter 4 Parameter List 40 Blank Page...
Страница 66: ...Chapter 5 Parameter Description Function Group 64...
Страница 67: ...Chapter 5 Parameter Description Function Group 65 Blank Page...
Страница 81: ...Chapter 5 Parameter Description I O Group 79 Blank Page...