Chapter 3 – Quick-Start Procedures
28
3.2
Operation Using Control Terminal – External Start, Stop and Speed Reference
1.
Confirm ‘Manual T/T’ in DRV 00.
2.
If different, as in section 3.1 of this chapter, select
‘Terminal’ in FUN 01 and ‘Terminal-1’ or Terminal-2’
in FUN 02.
3.
Install a potentiometer on terminals V1, VR and CM
as shown right below. Select ‘V1’ in FUN 20 to control the
speed by potentiometer alone.
4.
Set a frequency reference using the potentiometer.
Make sure to observe the set value in DRV 00.
5.
When a ‘4 - 20mA’ current source is used as the
frequency reference, use terminal I and CM.
Select ‘I’ in FUN 20 to control the speed by the
current source alone.
6.
To run the motor in the forward direction, close
the [FX] terminal to the [CM] terminal.
7.
To run the motor in the reverse direction, close
the [RX] terminal to the [CM] terminal.
DRV
¢º
Manual T/T
00 FWD 60.00 Hz
FUN
¢º
Freq. set
01 Terminal
FUN
¢º
Run/stop set
02 Terminal-1
FUN
¢º
V-I mode
20 V
10
?
, 1/2 W
EG
RST
FX RX
P2 P3 P4 P5
BX CM VR V1
P6 CM
I
FM
V2 IO
LM CM
FUN
¢º
V-I mode
20 I
EG
RST
FX RX
P2 P3 P4 P5
BX CM VR V1
P6 CM
I
FM
V2 IO
LM CM
4 - 20mA
Содержание SV030iH-2U
Страница 13: ...Chapter 1 Installation 11 STARVERT iH VARIABLE FREQUENCY DRIVE STARVERT IH SV132iH 4U SV160iH 4U...
Страница 26: ...Chapter 2 Operation 24 Blank Page...
Страница 34: ...Chapter 3 Quick Start Procedures 32 Blank Page...
Страница 42: ...Chapter 4 Parameter List 40 Blank Page...
Страница 66: ...Chapter 5 Parameter Description Function Group 64...
Страница 67: ...Chapter 5 Parameter Description Function Group 65 Blank Page...
Страница 81: ...Chapter 5 Parameter Description I O Group 79 Blank Page...