Chapter 6 - Troubleshooting Maintenance
82
6.3
Troubleshooting
Condition
Check Point
The Motor Does Not
Rotate
1)
Main circuit inspection:
?
Is the input (line) voltage normal? (Is the LED in the inverter is lit?)
?
Is the motor connected correctly?
2)
Input signal inspection:
?
Check the operating signal input to the inverter.
?
Check the forward and the reverse signal input simultaneously to the inverter?
?
Check the command frequency signal input to the inverter.
3)
Parameter setting inspection:
?
Is the reverse prevention (FUN 03) function set?
?
Is the operation mode (FU1N 02) set correctly?
?
Is the command frequency set to 0?
4) Load inspection:
?
Is the load too large or is the motor jammed? (Mechanical brake)
5) Other:
?
Is the alarm displayed on the keypad or is the alarm LED lit? (STOP LED blinks)
The Motor Rotates
in Opposite
Directions
?
Is the phase sequence of the output terminal U, V, W correct?
?
Is the starting signal (forward/reverse) connected correctly?
The Difference
Between the
Rotating Speed and
the Reference is
Too Large
?
Is the frequency reference signal correct? (Check the level of the input signal)
?
Is the following parameter setting is correct?
Lower Limit Frequency (FUN 27), Upper Limit Frequency (FUN 26), Analog Frequency Gain (FUN
20~23)
?
Is the input signal line influenced by external noise? (Use a shielded wire)
The Inverter Does
Not Accelerate or
Decelerate
Smoothly
?
Is the acceleration/deceleration time is set too short a period of time?
?
Is the load too large?
?
Is the Torque Boost (FUN 09~10) value is too high that the current limit function and the stall prevention
function do not operate?
The Motor Current
is Too High
?
Is the load too large?
?
Is the Torque Boost Value (manual) too high?
The Rotating Speed
Does Not Increase
?
Is the Upper Limit Frequency (FUN 26) value correct?
?
Is the load too large?
?
Is the Torque Boost (FUN 09~10) value too high that the stall prevention function (FUN 45~46) does not
operate?
The Rotating Speed
Oscillates When the
Inverter is
Operating.
1)
Load inspection:
?
Is the load oscillating?
2)
Input signal inspection:
?
Is the frequency reference signal oscillating?
3)
Other:
?
Is the wiring too long when the inverter is using V/F control? (Over 500m)
CAUTION
Risk of Electric Shock
– More than one disconnect switch may be required to de-energize
the equipment before servicing.
Содержание SV030iH-2U
Страница 13: ...Chapter 1 Installation 11 STARVERT iH VARIABLE FREQUENCY DRIVE STARVERT IH SV132iH 4U SV160iH 4U...
Страница 26: ...Chapter 2 Operation 24 Blank Page...
Страница 34: ...Chapter 3 Quick Start Procedures 32 Blank Page...
Страница 42: ...Chapter 4 Parameter List 40 Blank Page...
Страница 66: ...Chapter 5 Parameter Description Function Group 64...
Страница 67: ...Chapter 5 Parameter Description Function Group 65 Blank Page...
Страница 81: ...Chapter 5 Parameter Description I O Group 79 Blank Page...