Chapter 5 - Parameter Description (Function Group)
59
[Load Current Derating Curve]
[Motor i
2
t Characteristic Curve]
FUN 54: Number of motor poles
FUN
¢º
Pole number
54 4
Setting Range:
2 to 12
Factory Default:
4
This parameter selects the number of poles on the
motor. Used to display speed.
FUN 55: IPF Restart Selection
FUN 56: Speed Search Acceleration Time
FUN 57: Speed Search Deceleration Time
FUN 58: Speed Search Gain
FUN
¢º
IPF select
55 --- No ---
Setting Range:
No, Yes
Factory Default:
No
FUN
¢º
ss acc. time
56 5.0sec
Setting Range:
0.1 to 600sec
Factory Default:
5sec
FUN
¢º
ss dec. time
57 10.0sec
Setting Range:
0.1 to 600sec
Factory Default:
10sec
FUN
¢º
ss gain
58 100 %
Setting Range:
0 to 200%
Factory Default:
100%
These functions are used to permit automatic
restarting after Instantaneous Power Failure without
waiting for the motor to stop.
[FUN 55] selects the ‘IPF Restart’ function
[FUN 56] determines the acceleration time during
speed search.
[FUN 57] determines the acceleration time during
speed search.
[FUN 58] determines the gain during speed search.
n
The speed search gain and Acc/Dec time should be set after
considering the inertia moment (GD
2
) and magnitude of the
load.
100%
95%
65%
Output Current
20Hz
60Hz
Self-Cool
‘General’
Forced-Cool ‘Special’
Load Current [%]
Trip Time
FUN 52
1 Minute
100%
Содержание SV030iH-2U
Страница 13: ...Chapter 1 Installation 11 STARVERT iH VARIABLE FREQUENCY DRIVE STARVERT IH SV132iH 4U SV160iH 4U...
Страница 26: ...Chapter 2 Operation 24 Blank Page...
Страница 34: ...Chapter 3 Quick Start Procedures 32 Blank Page...
Страница 42: ...Chapter 4 Parameter List 40 Blank Page...
Страница 66: ...Chapter 5 Parameter Description Function Group 64...
Страница 67: ...Chapter 5 Parameter Description Function Group 65 Blank Page...
Страница 81: ...Chapter 5 Parameter Description I O Group 79 Blank Page...