Building Management Functions (IS-IPBML & IS-IPBMS Cards Only)
57
10.3.1 Select Modbus/TCP Security Mode Menu
The Select Modbus/TCP Security Mode menu is used to
restrict or allow Modbus access to the Web card.
Terminal Emulation
(Serial or TCP/IP Connection) / Telnet
1. Choose
IP Network Settings
from the Main Menu.
2. Choose
Management Protocol
from the IP Network
Settings Menu, then
Modbus/TCP Configuration
.
3. Choose
Modbus/TCP Security Mode
from the
Modbus/TCP Configuration menu.
4. Choose the security mode you wish to use from the
Select Modbus/TCP Security Mode menu:
•
Open
- allows any IP address to access the card
Web page.
•
Same Subnet
- allows any IP on the same Subnet
as the card to access the card Web page.
•
Trusted IPs
- allows a maximum of four IP
addresses to access the card Web page.
5. If the Trusted IP option is selected, you may specify up
to four IP addresses for access to the card Web page.
To do this:
a. Choose
Modbus/TCP Trusted IP list
from the
Modbus/TCP Configuration menu.
b. To add an address, enter
a
followed by a space and
the IP address, then press Enter. For example:
a 126.4.230.111
Each entry will be numbered—either
1
or
2
, as shown
at right. To make changes:
• To remove an address, enter
d
followed by a space and the number of the entry (
1
or
2
), then
press Enter. For example:
d 2
• To edit an address, enter
e
followed by a space, the number of the entry (
1
or
2
), a space and
the IP address, then press Enter. For example:
e 1 126.4.230.111
Web Interface
To specify the Modbus/TCP security mode through the Web interface:
• Click on the
Configure
tab, then
Modbus/TCP
in the left panel and finally
Edit
at right. If you
select
Trusted IP
as the Security Mode option, you may specify up to four IP addresses; click the
Clear
button to delete any entry. After making changes, click
Save
.
Management Protocol Menu
-------------------------
1: Modbus/TCP
enabled
2: Modbus/TCP Configuration
<ESC>: Cancel menu level
Please select a key ?>
Modbus/TCP Configuration Menu
------------------------------
1: Modbus/TCP Port
502
2: Modbus Write Access
Enabled
3: Modbus/TCP Security Mode
Open
4: Supported Data List
9539
<ESC>: Cancel menu level
Please select a key ?>
Select Modbus/TCP Security Mode
1. Open
2. Same Subnet
3. Trusted IPs
Select A Mode:
?>
Modbus/TCP Configuration Menu
------------------------------
1: Modbus/TCP Port
502
2: Modbus Write Access
Enabled
3: Modbus/TCP Security Mode
Trusted List
4: Supported Data List
9539
5: Modbus/TCP Trusted IP list
2
<ESC>: Cancel menu level
Please select a key ?> 5
1: 126.4.100.1
2: 126.4.100.2
3: 126.4.100.3
4: 126.4.100.4
<a>dd
<a xxx.xxx.xxx.xxx>
<d>elete <d n> or
<e>dit
<e n xxx.xxx.xxx.xxx>
Configure
tab
Modbus/
TCP
Edit
Security Mode