Factory Settings
42
7.2.2 Managed Device Settings
(Units with IS-WEBNXL, IS-WEBL,
IS-IPBML, IS-WEBS, IS-IPBMS Cards Only)
Use the Managed Device Settings menu for connection settings for
Liebert units with IS-WEBNXL, IS-WEBL, IS-IPBML, IS-WEBS or
IS-IPBMS cards (see
Table 1
).
Terminal Emulation (Serial or TCP/IP Connection) / Telnet
To specify connection settings for these units:
1. Choose
Factory Settings
from the Main Menu.
2. Choose
Advanced Communication Settings
from the Factory
Settings Menu.
3. Choose
Managed Device Settings
from the Advanced
Communication Settings Menu.
4. Choose
LAN Type
from the Local Node Settings Menu, then
specify which communication port the card will use:
• Choose
MS/TP
for 485 communications using the Liebert
IntelliSlot 485 connection port.
• Choose
BN/IP
for Ethernet communications using the
Ethernet RJ45 connection port.
5. Choose
Network Number
from the Local Node Settings Menu,
then specify the number of the network the card is connected to.
6. Choose
Node ID
from the Local Node Settings Menu, then specify the ID number of the server
the card is communicating with.
7.2.3 Router Settings
(Units with IS-WEBNXL, IS-WEBL, IS-IPBML,
IS-WEBS, IS-IPBMS Cards Only)
Use this menu to change router settings for Liebert units with
IS-WEBNXL, IS-WEBL, IS-IPBML, IS-WEBS or IS-IPBMS cards
(see
Table 1
).
Terminal Emulation (Serial or TCP/IP Connection) / Telnet
To specify router settings for these units:
1. Choose
Factory Settings
from the Main Menu.
2. Choose
Advanced Communication Settings
from the Factory
Settings Menu.
3. Choose
Router Settings
from the Advanced Communication
Settings Menu.
4. Choose
Router Enabled
, then turn the Protocol IP router on or
off by choosing:
•
Yes
to turn the router On (enable).
•
No
to turn the router Off (disable).
5. Choose 485 Network Number, then specify the appropriate
number.
6. Choose IP Network Number, then specify the appropriate
number.
Factory Settings Menu
----------------------
1: Advanced Communication
Settings
2: Agent Event Log
3: Reset to Factory Defaults
4: Support Information
5: Realtime Information
6: Task Stack Usage
<ESC>: Cancel menu level
Please select a key ?>
Advanced Communication Settings
Menu
--------------------------------
1: Local Node Settings
2: Managed Device Settings
3: Router Settings
4: Reset to Default
<ESC>: Cancel menu level
Please select a key ?>
Managed Device Settings Menu
-------------------------
1: Session Timeout(sec): 60
2: LAN Type: MS/TP
3: Network Number: 0
4: Node ID: 5
<ESC>: Cancel menu level
Please select a key ?>
Factory Settings Menu
----------------------
1: Advanced Communication
Settings
2: Agent Event Log
3: Reset to Factory Defaults
4: Support Information
5: Realtime Information
6: Task Stack Usage
<ESC>: Cancel menu level
Please select a key ?>
Advanced Communication Settings
Menu
--------------------------------
1: Local Node Settings
2: Managed Device Settings
3: Router Settings
4: Reset to Default
<ESC>: Cancel menu level
Please select a key ?>
Router Settings Menu
---------------------
1: Router Enabled: Yes
2: 485 Network Number: 1001
3: IP Network Number: 1000
<ESC>: Cancel menu level
Please select a key ?>