Factory Settings
41
7.2
Advanced Communication Settings
The Advanced Communication Settings menu offers the following options:
•
7.2.1 - Local Node Settings for Multiple Cards
•
7.2.2 - Managed Device Settings (Units with IS-WEBNXL, IS-WEBL, IS-IPBML,
IS-WEBS, IS-IPBMS Cards Only)
•
7.2.3 - Router Settings (Units with IS-WEBNXL, IS-WEBL, IS-IPBML, IS-WEBS,
IS-IPBMS Cards Only)
7.2.1 Local Node Settings for Multiple Cards
If you install two Liebert IntelliSlot cards of the same type—two
Web cards or two 485 cards—in a Liebert unit, you will need to
change the default address of one card. Each type of card has a
default MAC address and Node ID, as shown in
Table 23
.
Terminal Emulation (Serial or TCP/IP Connection) / Telnet
To access local node settings:
1. Choose
Factory Settings
from the Main Menu.
2. Choose
Advanced Communication Settings
from the Factory
Settings Menu.
3. Choose
Local Node Settings
from the Advanced
Communication Settings Menu.
4. Choose
Node ID
from the Local Node Settings Menu, then use the following guide and
Table 23
to make changes.
If the Liebert unit has two Liebert IntelliSlot cards of the same type—Web or 485—change the
address of one card:
• The default address for a Web card is
1
. Set the address of the second Web card to
2
.
• The default address for a 485 card is
2
. Set the address of the second 485 card to
1
.
Table 23
Factory default addresses
Type of Liebert
IntelliSlot Card
Default
MAC Address
Default
Node ID
Web card
0x01
1
485 card
0x02
2
Factory Settings Menu
----------------------
1: Advanced Communication
Settings
2: Reset to Factory Defaults
<ESC>: Cancel menu level
Please select a key ?>
Advanced Communication Settings
Menu
--------------------------------
1: Local Node Settings
2: Managed Device Settings
3: Reset to Default
<ESC>: Cancel menu level
Please select a key ?>
Local Node Settings Menu
-------------------------
1: Node ID: 1
2: Communication Rate: 38400
3: Maximum Master Address: 3
4: Maximum Retry Count: 5
5: Retry Interval(sec): 5
<ESC>: Cancel menu level
Please select a key ?>