58 Chapter 6 System O&M
DM Series 16kW Air Conditioner User Manual
Fan speed controller board
Bolt 2
Bolt 1
螺钉1(M4×10,共7颗)
螺钉2
风机转速控制器单板
散热片
Heat sink
Figure 6-6 Removing the fan speed controller board
6.2.2 Troubleshooting
See Table 6-3 for alarm troubleshooting.
Table 6-3 Table of alarm troubleshooting
Alarm
number ID
Alarm name
Cause
Troubleshooting
A00
Phase loss
alarm
1. One phase or two phase of
three-phase voltage is lost
1. Measure that the three-phase voltage is correct
2. The input connection is reversed
2. Check the input order of wire
3. The fan speed controller board has
hardware fault
3. Replace the fan speed controller board and compare
the result of two boards
A01
SCR
over
temperature
1. The fan cannot run normally
1. Check that the fan runs normally
2. The fan speed controller board has
hardware fault
2. Replace the fan speed controller board and compare
the result of two boards
A02, A03
Fan 1 over
temperature,
Fan 2 over
temperature
1. The fan cannot run normally
1. Check that the fan runs normally
2. The AC contactor supplying power
for fan has fault or its wire cuts off
2. Check the wiring of AC contactor; detect the auxiliary
contact state of AC contactor
3. Fan speed controller board has
hardware fault (the detecting circuit or
SCR power supplying circuit has fault)
3. Replace the fan speed controller board and compare
the result of two boards
A04
Pressure
sensor
failure
1. The pressure sensor is not installed
or its terminal connection is poor
1. Check the wiring of pressure sensor
2. Jumper caps are not used at shorting
terminals J17 and J18 of current
pressure sensor
2. Install the jumper cap when the current pressure
sensor is configured
3. The pressure sensor failed
3. Replace the pressure sensor and compare the result
of two boards
4. The fan speed controller board has
hardware fault
4. Replace the fan speed controller board and compare
the result of two boards
A05
EEPROM
read fault
The fan speed controller board has
hardware fault
Replace the fan speed controller board and compare
the result of two boards
A06
SCR
temperature
sensor
failure
1. The SCR temperature sensor is not
installed or its terminal connection is
poor
1. Check the wiring of SCR temperature sensors (J8
SCRTemp, see Figure 3-1 for whose position )
2. The SCR temperature sensor failed
2. Replace the SCR temperature sensor and compare
3. The fan speed controller has
hardware fault
3. Replace the fan speed controller board and compare
the result of two boards
A07
Abnormal
frequency
1. The frequency of power supply
voltage is wrong
2. The fan speed controller has
hardware fault
Replace the fan speed controller board and compare
the result of two boards