12 Chapter 2 Mechanical Installation
DM Series 16kW Air Conditioner User Manual
4. Be careful not to damage the waterproof layer and observe the local rules and regulations when the condenser is
installed on the roof of building.
5. Position the condenser higher than the indoor unit to ensure normal oil return.
6. Follow the installation arrows on the condenser for the installation direction.
2.5.2 Space Requirements
Note
1. A 4000mm clearance is required around the condenser air outlet.
2. The 600mm service spaces are required on the four sides of the condenser.
The condenser needs sufficient installation and service space around the installation place. The detailed space
requirements are shown in Figure 2-15 and Figure 2-16.
600
1200
450
Air flow
Air flow
Figure 2-15 Horizontal installation space requirement (unit: mm)
600
4000
Air flow
Figure 2-16 Vertical installation space requirement (unit: mm)
2.5.3 Mounting base dimension
Mounting base for horizontal installation
The mounting base for horizontal installation is shown in Figure 2-17 and the mounting base dimensions of each
model are listed in Table 2-3.