Chapter 5 Precision Air Conditioner Controller 41
Liebert_DM 16kW Air Conditioner User Manual
The tenth screen is the
Customer Input
menu, used to set alarm control and normal status. Select a submenu and
enter its interface, as shown in Figure 5-11. The
Alarm Control
items can be set to
On
,
Event
or
Off
. Their logic
definitions are the same as others. The
Normal Status
items can be set to
Open
or
Closed
.
Normal Status: Open
Alarm Control: On
Smoke Detected [2]
D00 I00
Fire Detected [2]
D00 I00
Normal Status: Open
Alarm Control: On
Customer Input 1 [2]
D00 I00
Normal Status: Open
Alarm Control: On
Customer Input 2 [2]
D00 I00
Normal Status: Open
Alarm Control: On
Figure 5-11 Customer input interface
Alarm set point
The
Alarm Set Point
menu is shown in Figure 5-12. The settings of the
Alarm Set Point
menu will not be lost when
the power fails. For detailed setting ranges of menu items, refer to
Appendix 6 Parameter Setting Table
.
Note
It is not recommended to change the defaults. If the change is necessary, change them under the guidance of trained professions.
Low TEMP Alarm: 15
High TEMP Alarm: 35 C
C
o
Alarm Set Point [2]
D01 I10
o
High HUM Alarm: 65%rH
Low HUM Alarm: 35%rH
Figure 5-12 Alarm set point interface
5.5.4 Set Point Control
Select
Main Menu 1/2
->
Set Point Control
in interface to enter the
Set Point Control
menu, as shown in Figure 5-13.
The setpoints will not be lost when the power fails. The menu is used to set the current running temperature & humidity
and their sensitivities of the AC unit. For detailed setting ranges, refer to
Appendix 6 Parameter Setting Table
.
TEMP Sensitivity: 06
Return Air TEMP: 24 C
C
o
Set Point Control [1]
D01 I10
o
Return Air HUM: 50%rH
HUM Sensitivity: 05%rH
Figure 5-13 Set point control interface