Chapter 5 Precision Air Conditioner Controller 45
Liebert_DM 16kW Air Conditioner User Manual
Sensor calibration
The
Sensor Calibration
menu is shown in Figure 5-27.
Sensor Calibration [3]
D01 I10
Return Air HUM: 00%rH
Return Air TEMP: 00 C
o
Figure 5-27 Sensor Calibration interface
Communication
The
Communication
menu is shown in Figure 5-28. For detailed setting ranges of the menu items, refer to
Appendix
6 Parameter Setting Table
.
Monitor ID: 001
Baud Rate: 9600
Protocol: YDN23
Communication [1]
D01 I10
Figure 5-28 Communication interface
Service mode
Select
System Menu 2/2
->
Service Mode
to enter the
Service Mode
menu, as shown in Figure 5-29.
The menu is used for the maintenance personnel to view whether the system is working normally.
Commission Mode
Manual Mode
Diagnostic Mode
Service Mode [2]
D01 I10
Figure 5-29 Service mode interface
The
Diagnostic Mode
,
Commission Mode
and
Manual Mode
menus have the same submenu. Taking
Diagnostic
Mode
menu as an example, the menu interface is shown in Figure 5-30.
Diagnostic Mode [2]
DeHUM: Off HUM: Off Cool2: Off
LLBP2: Off Heat2: Off
LLBP1: Off Heat1: Off
Fan: Off Fill: Off Cool1:Off
HGBP: Off Reserve: Off
D01 I10
Figure 5-30 Diagnostic mode interface
Note
1. Under the commission mode and manual mode, the
LLBP1
,
LLBP2
and
HGBP
are off.
2. Under the commission mode and diagnostic mode, after you press the ESC button to exit the mode, the system will restore the
normal control.
3. Under the manual mode, after you press the ESC button to exit the mode, all status can restore the normal control until the
controller is restarted after powered off.