1.4 Environment Requirements
1.4.1 Operation Environment
See Table 1-1 for the details.
Table 1-1 Operation enviroment requirement
Item
Requirement
Environment temperature
Indoor: 0
℃~
40
℃
Outdoor:
-
15
℃~+
45
℃
Protection level (outdoor unit)
IP55
Altitude
<1000m. Above that, derating is required
Operation voltage range
380V (-10% ~ +15%), 3N ~ 50Hz
1.4.2 Storage Environment
Table 1-2 Storage enviroment requirement
Item
Requirement
Storage environment
Indoor, no dust
Environment humidity
5%RH ~ 85%RH (non-condensing)
Environment
temperature
-
40
℃~+
70
℃
Storage time
Total transportation and storage time should not exceed 6 months. Otherwise, the performance needs
to be re-evaluated