26 Chapter 3 Electrical Installation
DM Series 16kW Air Conditioner User Manual
3.3 Wiring Of Outdoor Unit
3.3.1 Connecting Power Cables For Outdoor Unit
1. Identifying the cable specifications
Select the power supply cables and the start/stop signal cables of the condenser according to the fan rated operation
current (see Table 3-2) and the site conditions, such as the distance between indoor unit and condenser.
Table 3-2 Operation current of fan under 380V voltage
Condenser Model
Rated current (A)
DMC16M2
1.65
Note
1. The 20AWG (0.52mm
2
) start / stop signal cable of the condenser is recommended.
2. The protected tube or shielded line is required for the outdoor part of the connection cable between the indoor unit and the
condenser. The ground cable should be connected to the ground nearby, and the length cannot exceed 3m.
3. The cables cannot contact with hot objects, such as the copper tube and water pipe without insulation, to avoid damaging the
insulation layers.
4. The cables should be connected in accordance with the local regulations.
2. Connecting cables
See Figure3-5 and
Appendix 3 Circuit Diagram of DMC16M2
for the connections of external power cables.
Waterproof connector of external
外部电源进
线防水接头
外部电源接入端(单风机)
风机转速控制器单板
Accessing terminal of external
Fan speed controller board
power supply (single fan)
power accessing lines
Water joint of external
power cables
Figure 3-5 Connection figure of single fan external power cables (taking LDF42 for example)
Note
1. The external power lines and compressor signal lines enter the electrical controlling box through the water joint of external
power cables whose inside diameter is
Φ
10mm.
2. After connecting the external power lines, the waterproof sealant treatment is required to ensure the good waterproof
performance of electrical controlling box.
3. The phase order of three-phase AC input (L1, L2, L3) must be correct. Otherwise, the fan speed controller will generate the
phase loss alarm, and there will be no AC output.
3.3.2 Connecting Control Signal Cables Of Outdoor Unit
The wiring terminals are located on the fan speed controller board (see Figure3-5). Their distribution is shown in
Figure3-6 and the definitions are listed in Table3-3. Refer to
Appendix 3 Circuit Diagram of DMC16M2
for detailed
connections.