32) Liquid Temperature (Chiller)
h
Valid Range
Output
Function
Liquid Temperature display
Using NV
network variable : SNVT_temp_p, nvoLiquidTemp1,
nvoLiquidTemp2, nvoLiquidTemp3
Operation Liquid Temperature monitor
NV
Operation
SNVT_temp_p
-42 ~ 95 °C
33) STD 1 Comp Discharge (Chiller)
h
Valid Range
Output
Function
STD Comp Discharge display
Using NV
network variable : SNVT_temp_p, nvoStd1CDTemp1,
nvoStd1CDTemp2, nvoStd1CDTemp3
Operation STD Comp Discharge monitor
NV
Operation
SNVT_temp_p
0 ~ 100 °C
34) STD 2 Comp Discharge (Chiller)
h
Valid Range
Output
Function
STD Comp Discharge display
Using NV
network variable : SNVT_temp_p, nvoStd2CDTemp1],
nvoStd2CDTemp2, nvoStd2CDTemp3
Operation STD Comp Discharge monitor
NV
Operation
SNVT_temp_p
0 ~ 100 °C
35) Product Group Information (Chiller)
h
Valid Range
Output
Function
Product Group Information display
Using NV
network variable : SNVT_count, nvoChillerGroup
Operation Product Group Information monitor
NV
Operation
SNVT_count
2
36) Product Type Information (Chiller)
h
Valid Range
Output
Function
Product Type Information display
Using NV
network variable : SNVT_count, nvoChillerType
Operation Product Type Information monitor
NV
Operation
SNVT_count
0 ~ 255