Chiller input/output
1) On/Off (Chiller)
h
Valid Range
NV
Field
Operation
SNVT_switch
value
not used (set in 0% usually)
state
0 = OFF
1 = ON
Input
Function
On/Off input
Using NV
network variable : SNVT_switch, nviOnOff
Operation On/Off control
Output
Function
On/Off display
Using NV
network variable : SNVT_switch, nvoOnOff
Operation On/Off monitor
2) Alarm Release (Chiller)
h
Valid Range
NV
Field
Operation
SNVT_switch
value
not used (set in 0% usually)
state
0 = OFF
1 = ON
Input
Function
Alarm Release input
Using NV
network variable : SNVT_switch, nviAlarmRelease
Operation Alarm Release control
Output
Function
Alarm Release display
Using NV
network variable : SNVT_switch, nvoAlarmRelease
Operation Alarm Release monitor
3) Cooling Water Frost Protection (Chiller)
h
Valid Range
NV
Field
Operation
SNVT_switch
value
not used (set in 0% usually)
state
0 = OFF
1 = ON
Input
Function
Cooling Water Frost Protection input
Using NV
network variable : SNVT_switch, nviCWFrostP
Operation Cooling Water Frost Protection control
Output
Function
Cooling Water Frost Protection display
Using NV
network variable : SNVT_switch, nvoCWFrostP
Operation Cooling Water Frost Protection monitor