NOTES
ENGLISH
127
Function Block
n
Air conditioner Objects
• You can enable control and monitoring as shown in the figure for one air conditioner unit.
• The network variable can differ from the actual. (Refer to the XIF file for correct network variable.)
Indoor
unit
Network
Variables
SCC
(8500)FB
Indoor
unit
Network
Variables
SCC
(8500)FB
①
Standard Function Block
②
General Function Block
Control
On/Off
Operation Mode
Lock
Temperature
Fan Level
Fan Direction Auto
Mode Lock
Fan Level Lock
Temperature Lock
Temperature Lower Limit
Temperature Higher Limit
Peak Convert Cycle
Peak Setting
Temperature Unit
Total Temperature Lock
Total OnOff
Total Temperature
Monitoring
On/Off
Operation Mode
Lock
Temperature
Fan Level
Fan Direction Auto
Mode Lock
Fan Level Lock
Temperature Lock
Temperature Lower Limit
Temperature Higher Limit Product Type
Product Address
Current Temperature
Error monitor
Power
Peak Convert Cycle
Peak Setting
Temperature Unit
Peak Current Operating Percent
Total Accumulate Power
NOTE
!
• The appendix carries information necessary for interfacing with BMS and not necessary for
actual installation.
SNVT_switch
nviOnOff
SNVT_hvac_mode
nviHeatCool
SNVT_switch
nviLock
SNVT_temp_p
nviSetPoint
SNVT_switch
nviFanSpeedCmd
SNVT_switch
nviSwing_Heater
SNVT_switch
nviModlok
SNVT_switch
nviFanlok
SNVT_switch
nviTmplok_Humid
SNVT_temp_p
nviLow_HW_Tmp
SNVT_temp_p
nviUp_Tmp
SNVT_count
nviPeakSwTime
SNVT_lev_percent
nviPeakTgtRate
SNVT_Switch
nviTempUnit
SNVT_switch
nviAllTemplock
SNVT_switch
nviTotalOnOff
SNVT_temp_p
nviTotalTemp
SNVT_count
nvoPeakSwTime
SNVT_lev_percent
nvoPeakTgtRate
SNVT_Switch
nvoTempUnit
SNVT_lev_percent
nvoPeakCurRate
SNVT_count_f
nvoTotalAccuPw
SNVT_switch
nvoOnOff
SNVT_hvac_mode
nvoHeatCool
SNVT_switch
nvoLock
SNVT_temp_p
nvoSetPoint
SNVT_switch
nvoFanSpeed
SNVT_switch
nvoSwing_Heater
SNVT_switch
nvoModlok
SNVT_switch
nvoFanlok
SNVT_switch
nvoTmplok_Humid
SNVT_temp_p
nvoLow_HW_Tmp
SNVT_temp_p
nvoUp_Sol_Tmp
SNVT_count
nvoPType
SNVT_count
nvoPAddr
SNVT_temp_p
nvoSpaceTemp
SNVT_hvac_status
nvoUnitStatus
SNVT_count_f
nvoAccuPw