![LG V-NET PLNWKB000 Скачать руководство пользователя страница 178](http://html.mh-extra.com/html/lg/v-net-plnwkb000/v-net-plnwkb000_installation-and-user-manual_212727178.webp)
17
8
NOTES
ENGLISH
28) Comp. Discharge Temperature (Chiller)
h
Valid Range
Output
Function
Comp. Discharge Temperature display
Using NV
network variable : SNVT_temp_p, nvoInvCDTemp1,
nvoInvCDTemp2, nvoInvCDTemp3
Operation Comp. Discharge Temperature monitor
NV
Operation
SNVT_temp_p
0 ~ 100 °C
29) Comp. Suction Temperature (Chiller)
h
Valid Range
Output
Function
Comp. Suction Temperature display
Using NV
network variable : SNVT_temp_p, nvoCompSuctTemp1,
nvoCompSuctTemp2, nvoCompSuctTemp3
Operation Comp. Suction Temperature monitor
NV
Operation
SNVT_temp_p
0 ~ 100 °C
30) EEV Status (Chiller)
h
Valid Range
Output
Function
EEV Pulse display
Using NV
network variable : SNVT_lev_percent, nvoEEVStatus1,
nvoEEVStatus2, nvoEEVStatus3
Operation EEV Status monitor
NV
Operation
SNVT_lev_percent
0 ~ 100
31) HEX Temperature (Chiller)
h
Valid Range
Output
Function
HEX Temperature display
Using NV
network variable : SNVT_temp_p, nvoHexTemp1L, nvoHexTemp2L,
nvoHexTemp3L, nvoHexTemp1R, nvoHexTemp2R, nvoHexTemp3R
Operation HEX Temperature monitor
NV
Operation
SNVT_temp_p
-42 ~ 95 °C