Air conditioner, ERV, ERV DX, AWHP General input/output
1) Peak Convert Cycle (Air conditioner)
156
NOTES
ENGLISH
h
Valid Range
Input
Function
Peak Convert Cycle input
Using NV
network variable : SNVT_count, nviPeakSwTime
Operation Peak Convert Cycle control
Output
Function
Peak Convert Cycle display
Using NV
network variable : SNVT_count, nvoPeakSwTime
Operation Peak Convert Cycle monitor
NV
Operation
SNVT_count
300~900 sec
2) Peak Setting (Air conditioner)
h
Valid Range
Input
Function
Peak Setting input
Using NV
network variable : SNVT_lev_percent, nviPeakTgtRate
Operation Peak Setting contorl
Output
Function
Peak Setting display
Using NV
network variable : SNVT_lev_percent, nvoPeakTgtRate
Operation Peak Setting monitor
NV
Operation
SNVT_lev_percent
0 ~ 100 %
3) Temperature Unit (Air conditioner, ERV DX)
h
Valid Range
Input
Function
Temperature Unit input
Using NV
network variable : SNVT_switch, nviTempUnit
Operation Temperature Unit control
Output
Function
Temperature Unit display
Using NV
network variable : SNVT_switch, nvoTempUnit
Operation Temperature Unit monitor
NV
Field
Operation
SNVT_switch
value
not used (set in 0% usually)
state
0 = Celcius
1 = Fahrenheit