78
MultiSITE MS8250 V
AV Room Controllers
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp.
1/4 LUA
LUA program’s name:
User program
Program:
if not init then
init=true
delay=0
end
if ME.BV1==1 then
ME.BO98=1
delay=60
Body of the LUA Script
Title of LUA Script
2/4 LUA
Debug log:
Program cmd
Program status
Program error
Run
Running
No error
Table 50: LUA Settings Parameter Details.
Configuration Parameters Default Value
Significance and Adjustments
Program cmd (Program Command)
Default Value: Run
Run: LUA script activated and runs continuously until deactivated.
Stop: LUA script deactivated.
Choices: Stop or Run.
Program Status
Default Value: Idle
Read Only
Running: LUA script active.
Halted: LUA script stopped and not active.
Idle: LUA script is running but not currently performing any actions.
Waiting: LUA script running and waiting for a response.
Uploading: LUA script currently unloading from the Room Controller.
Loading: LUA script currently loading to the Room Controller.
Display Readings: Idle, Loading, Running, Waiting, Halted, Unloading.
Program Error
Default Value: No error
Read Only
No error: No errors in LUA script.
Syntax: Syntax error in LUA script detected.
Runtime: Runtime error occurred while running LUA script.
Memory: Device has run out of memory for the script.
Display Readings: No error, Syntax, Runtime, Memory.
LUA Settings
The LUA settings screens show information about any custom LUA script uploaded to the Room Controller. LUA scripts are not program-
mable on the Room Controllers. LUA scripts can be uploaded to the Room Controller via the Uploader Tool or via BACnet.
LUA SCREENS
LUA Settings
Figure 63: LUA Settings Displays.